A2-4
IM 34M06H62-02E 3rd Edition : Jul.16
2015-00
Table A2.4 Instrument Range and Accuracy (for low resolution operation with SW1-1 set to OFF) 2/4
Input
Category
Input Type
*1
Instrument Range
Input Type Selector Switch
*3
Software
Setting
Accuracy
*4
Resolution
*2
SW1-3 SW1-4 SW5
Software setting ON OFF 0
Instrument ranges may be specified by
software using one of the following codes.
Thermocouple
K
*5
-200 to1370C
ON OFF
1 33 ($21)
2C
*5
1C
*5
-200 to1000C 2 34 ($22)
-200 to500C 3 35 ($23)
2C 1C
J
-200 to 1200C 4 36 ($24)
-200 to 500C 5 37 ($25)
T -270 to 400C 6 38 ($26)
2C
1C
B
0 to 1600C 7 39 ($27)
2C
1C
S
0 to 1600C 8 40 ($28)
2C 1C
R
0 to 1600C 9 41 ($29)
N -200 to 1300C A 42 ($2A)
2C
1C
E -270 to 1000C B 43 ($2B)
2C
1C
L -200 to 900C C 44 ($2C)
2C 1C
U -200 to 400C D 45 ($2D)
W
0 to 1600C E 46 ($2E)
Platinel 2 0 to 1390C F 47 ($2F)
RTD
JPt100
-200 to 500C
ON ON
0 48 ($30)
2C 1C
-200 to 200C 1 49 ($31)
0 to 300C 2 50 ($32)
0.0 to 150.0C 3 51 ($33)
0.3C 0.1C
Pt100
-200 to 850C 4 52 ($34)
2C 1C
-200 to 500C 5 53 ($35)
-200 to 200C 6 54 ($36)
0 to 300C 7 55 ($37)
0.0 to 150.0C 8 56 ($38)
0.3C 0.1C
*1: Applicable standard is JIS/IEC/DIN (ITS-90) for thermocouples and RTD.
*2: For thermocouples K, B, S, R, and W, input ranges may be set wider than their instrument range (see the notes below). Furthermore, the
actual range for an acceptable input is the input range5%.
*3: When you turn on the power after changing the hardware switch settings, data stored in the EEPROM is initialized to follow the switch
settings.
*4: This accuracy applies if the ambient temperature is 25 5C and the input value is within the instrument range. If the input type is
thermocouple and reference junction compensation is used, you should also take into consideration the accuracy of the reference
junction compensation.
*5: For K-type thermocouples, the upper and lower input range limits may be set from -270 to 1370C. The accuracy and resolution depend
on measured temperatures as follows:
-270 to -200C: Neither accuracy nor resolution is guaranteed.
*6: For T-type thermocouples, the accuracy and resolution depend on measured temperatures as follows:
-270 to -200C: 4C accuracy, 1C resolution
*7: For B-type thermocouples, the upper and lower input range limits may be set from 0 to 1800C. The accuracy and resolution depend on
measured temperatures as follows:
0 to 300C: Neither accuracy nor resolution is guaranteed.
300 to 900C: 3C accuracy, 1C resolution
*8: For S-type and R-type thermocouples, the upper and lower input range limits may be set from 0 to 1700C.
*9: For N-type thermocouples, the accuracy and resolution depend on measured temperatures as follows:
-200 to 0C: 3C accuracy, 1C resolution
*10: For E-type thermocouples, the detailed accuracy and resolution are as follows:
-270 to -200C: 8C accuracy, 2C resolution
-200 to 1000C: 2C accuracy, 1C resolution
*11: For W-type thermocouples, the upper and lower input range limits may be set from 0 to 2300C.