IM 04L51B01-17EN
Commands and Responses
2
SRangeDI
Measurement Range of DI Channel
Sets the measurement range of a DI channel.
Unused Channels
Syntax
SRangeDI,p1,p2
p1
Channel number
p2
Input type (Skip)
Channels That Are Not Delta, Scaling, Pulse Input
Syntax
SRangeDI,p1,p2,p3,p4,p5,p6
p1
Channel number
p2
Input type (DI)
p3
Fixed at “-.”
P4
Calculation type (Off)
p5
Span lower limit (0 to 1)
p6
Span upper limit (0 to 1)
Delta Channels
Syntax
SRangeDI,p1,p2,p3,p4,p5,p6,p7
p1
Channel number
p2
Input type (DI)
p3
Fixed at “-.”
P4
Calculation type (Delta)
p5
Span lower limit (0 to 1)
p6
Span upper limit (0 to 1)
p7
Reference channel number
Scaling Channels
Syntax
SRangeDI,p1,p2,p3,p4,p5,p6,p7,p8,p
9,p10
p1
Channel number
p2
Input type (DI)
p3
Fixed at “-.”
P4
Calculation type (Scale)
p5
Span lower limit (0 to 1)
p6
Span upper limit (0 to 1)
p7
Decimal Place (0 to 5)
p8
Scaling lower limit
p9
Scaling upper limit
p10
Unit (up to 6 characters, UTF-8)
Pulse Input Channels
Syntax
SRangeDI,p1,p2,p3,p4,p5,p6
p1
Channel number
p2
Input type (Pulse)
p3
Fixed at “-.”
P4
Math type (Off)
p5
Span lower limit (0 to 999999)
p6
Span upper limit (0 to 999999)
Query
SRangeDI[,p1]?
Example Measure 0 to 1 on channel 0103. No scaling.
SRangeDI,0103,DI,-,Off,0,1
Description
• You cannot use this command to configure settings
while recording is in progress.
• You cannot use this command to configure settings
while computation is in progress.
• p2=Pulse can be specified when the math function (/
MT) is installed.
• If p2=Pulse, p4=Delta or Scale cannot be specified.
• p2=Pulse cannot be specified when the operation
mode of the DI module is set to Remote.
• You cannot use this command to configure settings
when the measurement mode is set to high speed.
SRangeDO
DO Channel Operation
Sets the DO channel operation.
Alarm Output
Syntax
SRangeDO,p1,p2,p3,p4,p5,p6,p7,p8
,p9
p1
Channel number
p2
Output type (Alarm)
p3
Span lower limit (0 to 1)
P4
Span upper limit (0 to 1)
p5
Unit (up to 6 characters, UTF-8)
p6
Energize or de-energize
Energize
Energize the relay (DO
channel) during output.
De_Energize
De-energize the relay
(DO channel) during
output.
p7
Operation
And
Operate when all set alarms are
in the alarm state.
Or
Operate when any of the set
alarms are in the alarm state.
p8
Hold or nonhold
Hold
Hold output until an
alarm ACK operation.
Nonhold
Clear output when the
alarm is cleared.
p9
Relay (DO channel) action on
acknowledge (Normal, Reset)
Alarm Output (Reflash)
Syntax
SRangeDO,p1,p2,p3,p4,p5,p6,p7,p8
,p9
p1
Channel number
p2
Output type (Alarm)
p3
Span lower limit (0 to 1)
P4
Span upper limit (0 to 1)
p5
Unit (up to 6 characters, UTF-8)
p6
Energize or de-energize
Energize
Energize the relay (DO
channel) during output.
De_Energize
De-energize the relay
(DO channel) during
output.
p7
Action (Reflash)
p8
Reflash time (500ms, 1s, 2s)
p9
Relay (DO channel) action on
acknowledge
Manual Output
Specifies the output value.
2.4 Setting Commands