2-33
IM 04L51B01-17EN
Commands and Responses
1
2
App
SPresetAO
Sets the Preset Action
Sets the preset action of an AO channel.
Syntax
SPresetAO,p1,p2,p3,p4
p1
Channel number
p2
Action at power-on (Last, Preset)
Last
Hold previous value
Preset
Output preset value
p3
Action on error (Last, Preset)
Last
Hold previous value
Preset
Output preset value
p4
Action on stop (Last, Preset)
Last
Hold previous value
Preset
Output preset value
Query
SPresetAO[,p1]?
Example At power-on, replace the channel 0001 value
with the preset value of 0.5.
SPresetAO,0001,Preset,0.5
Description
You cannot use this command to configure settings
while recording is in progress.
You cannot use this command to configure settings
while computation is in progress.
“Action on stop” indicates a scanning stopped, math
stopped, or re-transmission off condition.
SMathBasic
Math Action (/MT)
Sets the basic operation of math channels.
Syntax
GX/GP
SMathBasic,p1,p2,p3,p4,p5
GM
SMathBasic,p1,p2,p3,p4,p5,p6,p7
p1
Indication on computation error
+Over
Display the computed
value as +Over.
-Over
Display the computed
value as -Over.
p2
SUM and AVE computation when overflow
data is detected
Error
Sets the computation
result to computation
error.
Skip
Discards the data that
overflowed and continues
the computation.
Limit
Computes by substituting
upper or lower limit
values in the data that
overflowed.
For channels that do
not have linear scaling
specified, the upper
or lower limit of the
measuring range
For channels that
have linear scaling
specified, the scaling
upper or lower limit
For math channels,
the specified span
upper or lower limit.
p3
MAX, MIN, and P-P computation when
overflow data is detected
Over
Computes using data that
overflowed.
Skip
Discards the data that
overflowed and continues
the computation.
P4
START/STOP key action
(GX/GP: Off, Start/Stop, Reset+Start/
Stop)
(GM: Off)
Off
Computation does not
start even when recording
starts.
Start/Stop
Computation starts when
recording starts.
Reset+
Start/Stop
Computation resets and
starts when recording
starts.
p5
PSUM over operation (GX/GP)
Rotate
Rotate
Over
Over
P5
START key action (Off, Start, Reset+Start)
(GM)
Off
Recording starts but not
computation.
Start
Computation starts when
recording starts.
Reset+Start
Computation resets and
starts when recording
starts.
P6
STOP key action (Off, Stop)
Off
Recording stops but not
computation.
Stop
Computation stops when
recording stops.
p7
PSUM over operation (GM)
Rotate
Rotate
Over
Over
Query
SMathBasic?
Example Set the indication on computation error to
“+Over,” computation when overflow data is
detected to “Skip,” and start computation when
recording starts.
SMathBasic,+Over,Skip,Skip,Start/
Stop
Description
You cannot use this command to configure settings
while recording is in progress.
You cannot use this command to configure settings
while computation is in progress.
p5 and p6 are invalid parameters for the GX/GP.
When the multi batch function (/BT) is enabled, p4 is
fixed to Off.
2.4 Setting Commands