2-60
IM 04L51B01-17EN
SKdcCnct
KDC Connection Destination (/AS)
Sets the KDC server for the password management.
Syntax
SKdcCnct,p1,p2,p3
p1
Connection destination (Primary,
Secondary)
Primary
Primary server
Secondary
Secondary server
p2
KDC server name (up to 64 characters,
ASCII)
p3
Port number (1 to 65535)
Query
SKdcCnct[,p1]?
Example For the primary KDC server, assign the server
name “KdcControl1” and port number 88.
SKdcCnct,Primary,KdcControl1,88
SAuthKey
Certification Key (/AS)
Sets the certification key that is used during password
management authentication.
Syntax
SAuthKey,p1,p2,p3,p4
p1
Host principal (up to 20 characters, ASCII)
p2
Realm name (up to 64 characters, ASCII)
p3
Password (up to 20 characters, ASCII)
p4
Encryption (ARC4, AES128, AES256)
Query
SAuthKey?
Example Set the password of host principal “GX10_001”
realm “REALM01” to “gDcbwT5,” and the
encryption (the same as the server) to
AES128.
SAuthKey,GX10_001,REALM01,gDcbwT5,
AES128
Description
• Slashes and ampersands cannot be used in p1 or p2.
SDarwinCnvCh
Darwin Channel Conversion (Darwin
compatible communication)
Replace Darwin channels with recorder channels.
Syntax
SDarwinCnvCh,p1
p1
Darwin model
Standalone
Stand-alone type
Extension
Extended type
Query
SDarwinCnvCh?
Example Replace DA100 stand-alone type channels to
recorder channels.
SDarwinCnvCh,Standalone
SDarwinPortLimit
Port limitation of DARWIN compatible
communication
If port limitation is on, port number 34151 only allows
reading of instantaneous data.
Syntax
SDarwinPortLimit,p1
p1
Port limitation on/off (On/Off)
On
Instantaneous data reading only
on 34151.
Off
No limitations on 34150 or 34151.
Query
SDarwinPortLimit?
Example Set port number 34151 to instantaneous data
reading only.
SDarwinPortLimit,On
Description
• The following applies when port limitation is set to On.
• When connected via Ethernet
Only instantaneous data reading is possible on port
number 34151. Configuration, control, and operation
are not possible.
• When connected via serial communication
Only the commands that can be used on a Ethernet
connection through port 34150 are valid.
SSLMPClient
SLMP client operation (/E4)
Sets the SLMP client operation.
Syntax
SSLMPClient,p1,p2,p3,p4
p1
Data code (Binary, ASCII)
p2
Read cycle (100ms, 200ms, 500ms, 1s,
2s, 5s, 10s, 20s, 30s, 1min)
p3
Timeout value (250ms, 500ms, 1s, 2s, 3s,
4s, 5s, 10s, 20s, 30s, 1min)
p4
Recovery time (Off, 5s, 10s, 30s, 1min,
2min, 5min)
Query
SSLMPClient?
Example Set the data code to binary, read cycle to 500
ms, timeout value to 1 s, and recovery time to
2 min.
SSLMPClient,Binary,500ms,1s,2min
SSLMPCList
SLMP connection destination server (/
E4)
Sets the SLMP client connection destination server.
Syntax
SSLMPCList,p1,p2,p3
p1
Connection destination number (1 to 16)
p2
Server name (up to 64 characters, ASCII)
p3
Port number (1 to 65535)
Query
SSLMPCList[,p1]?
Example Connect to the server at connection
destination number 1. Set the server name to
“SMARTDAC” and the port number to 2020.
SSLMPCList,1,"SMARTDAC",2020
2.4 Setting Commands