2-67
IM 04L51B01-17EN
Commands and Responses
2
SMultiKind
Multi Panel [GX/GP]
Set the screens to display on the multi panel.
Syntax
SMultiKind,p1,p2,p3,p4
p1
Registration number (1 to 20)
p2
Screen position (1 to 6)
p3
Screen type
Trend
Trend
Digital
Digital
Bar
Bar graph
Overview
OVERVIEW
Alarm
Alarm summary
Message
Message summary
Memory
Memory summary
Report
Report summary
Modbus-M
Modbus master status
Mosbus-C
Modbus client status
Watt
WT communication status
Switch
Internal switch status
Action-
Log
Event log
Error-Log
Error log
Commu-Log
Communication log
Ftp-Log
FTP log
Web-Log
Web log
Mail-Log
Mail log
Modbus-
Log
Modbus log
Sntp-Log
SNTP log
Dhcp-Log
DHCP log
Network
Network information
SLMP-C
SLMP client status (/E4)
SLMP-Log
SLMP log (/E4)
Reminder
Reminder (/AH)
ControlGroup
Control group
ControlSummary
Control summary
ControlAlarmSummary
Control alarm
summary
ControlOverview
Control overview
P4
Group number
If p3=Trend, Digital, or Bar
Display group number
If p3=ControlGroup
Control group number
Query
SMultiKind[,p1[,p2]]?
Example Display the bar graph of display group 8 in
screen position 3 of the registration number 1
panel.
SMultiKind,1,3,Bar,8
Description
• This command is only valid for the GX20/GP20.
• Report is an option (/MT).
• Modbus-M and Modbus-C are an option (/MC).
• Watt is an option (/E2).
• Custom display screen (/CG) cannot be shown in a
multi panel.
• This command can be used only when the multi batch
function (/BT) is disabled.
• ControlGroup, ControlSummary,
ControlAlarmSummary, and ControlOverview are valid
when the PID control module is installed.
SHomeMonitor
Standard Screen Information [GX/GP]
Sets the standard screen display information.
Syntax
SHomeMonitor,p1,p2
p1
Information type (see the table of the
SMonitor command)
p2
Status (see the table of the SMonitor
command)
Query
SHomeMonitor[,p1]?
Example Set the trend display to all-channel display.
SHomeMonitor,Trend,All
2.4 Setting Commands