2-73
IM 04L51B01-17EN
Commands and Responses
2
SMasterScanGrp
Master Scan Interval
Sets the master scan interval when the measurement
mode is set to dual interval.
Syntax
SMasterScanGrp,p1
p1
Scan group number (1 or 2)
Query
SMasterScanGrp?
Example Set display group 5 to scan group 2.
SMasterScanGrp,2
Description
• You can set this command when the dual interval
function is enabled.
SCtrlMode
Control Mode
Sets the control mode.
Syntax
SCtrlMode,p1,p2,p3,p4
p1
Unit number
p2
Module number
p3
Mode (Single, Cascade, PVSwitching)
Single
Single loop control
Cascade
Cascade control
PVSwitching
PV switching
p4
PV switching condition (when p3 is
PVSwitching)
LowRange
Switch within range
(Low side)
HighRange
Switch within range
(High side)
PVHigh
Switch at PV high
limit
Signal
Switch using DI
Query
SCtrlMode[,p1,p2]?
Example Set the control mode of the PID module with
module number 2, connected to the main unit,
to PV switching and the switching condition to
switch using DI.
SCtrlMode,0,2,PVSwitching,Signal
Description
• This command is valid when a PID Control Module is
installed.
SCtrlScan
Control Period
Sets the control period.
Syntax
SCtrlScan,p1,p2,p3
p1
Unit number
Fixed to “–”.
p2
Module number
Fixed to “–”.
p3
Control period (100ms, 200ms)
Query
SCtrlScan?
Example Set the control period to 100ms.
SCtrlScan,-,-,100ms
Description
• This command is valid when a PID Control Module is
installed.
SCtrlAction
Control
Sets the control.
Syntax
SCtrlAction,p1,p2,p3
p1
Unit number
p2
Module number
p3
Power recovery action
RESTART_CONT
Continue
RESTART_MAN
Manual
RESTART_AUTO
Auto
RESTART_RESET
Reset
Query
SCtrlAction[,p1,p2]
Example Set the power recovery action of module
number 2 connected to the main unit to
manual.
SCtrlAction,0,2,RESTART_MAN
Description
• This command is valid when a PID Control Module is
installed.
• You can set p3 to RESTART_RESET when the
program control function (/PG option) is enabled.
SCtrlType
Control Type
Sets the control type.
Syntax
SCtrlType,p1,p2
p1
Loop number
p2
Control Type
PID
PID Control
ONOFF
ON/OFF control
Query
SCtrlType[,p1]?
Example Set the control type of loop number L022 to
ON/OFF control.
SCtrlType,L022,ONOFF
Description
• This command is valid when a PID Control Module is
installed.
2.4 Setting Commands