JOHNSON CONTROLS
114
FORM 201.23-NM2
ISSUE DATE: 09/25/2020
SECTION 6 - TECHNICAL DATA
Models YCIV0177E/V, YCIV0177S/P/H, YCIV0187E/V and YCIV0187S/P/H
DIMENSIONS - 2 AND 3 COMPRESSOR ENGLISH (CONT'D)
VIEW C-C
VIEW B-B
12"
3" WIDE X 13 1/2" HIGH
1 1/2"
4"
POWER ENTRY
10" WIDE X 13" HIGH
1 3/4"
POWER ENTRY IS ON BOTTOM OF PANEL
88 1/8"
28 1/8" (EDGE OF UNIT
TO COOLER
CONNECTION)
19 1/8"
C
C
B
B
VIEW A-A
POWER ENTRY
10" WIDE X 13"
HIGH
YCIV A B
0177E/V 88.1" 274.0"
0177S/P/H 80.0" 230.0"
0187E/V 88.1" 274.0"
0187S/P/H 88.1" 274.0"
19 -1/8"
28-1/8" (EDGE OF
UNIT TO COOLER
CONNECTION)
Placement on a level surface of free of
obstructions (including snow, for winter
operation) or air circulation ensures rated
performance, reliable operation, and ease
of maintenance. Site restrictions may
compromise minimum clearances indi-
cated below, resulting in unpredictable
airow patterns and possible diminished
performance.
Johnson Controls unit controls will op-
timize operation without nuisance high-
pressure safety cutouts; however, the
system designer must consider potential
performance degradation. Access to the
unit control center assumes the unit is no
higher than on spring isolators. Recom-
mended minimum clearances: side to wall
– 2 m; rear to wall – 2 m; control panel to
end wall – 1.2 m; top – no obstructions
whatsoever; distance between adjacent
units – 3 m. No more than one adjacent
wall may be higher than the unit.