JOHNSON CONTROLS
235
SECTION 8 - MICROPANEL
FORM 201.23-NM2 
ISSUE DATE: 09/25/2020
8
SYSTEM SAFETIES (FAULTS)
System Safety (Fault) Operation
System safeties are faults that cause individual systems 
to be shut down if a safety threshold is exceeded for 3 
seconds. System faults are auto reset faults in that the 
system will be allowed to restart automatically after the 
120 second anti-recycle timer times out. The only ex-
ception is after any 3 faults on the same system occur 
within 90 minutes, that system will be “locked out” on 
the last fault. The lockout condition requires a manual 
reset using the system switch. The respective system 
switch must be cycled off and on to clear the lockout 
fault. See Table 21 on page 262 for the programmable 
limits for many of the cutouts.
When multiple systems are operating and a system 
fault occurs, the running systems will ramp down and 
the faulted system will be shut off and the previously 
operating will restart if required after the fault clears 
and/or the 120 second anti-recycle timer times out.
In the descriptions of the fault displays that follow, the 
fault message will show a YYYYYYYY to indicate 
that a system is in a “FAULT” condition and will re-
start when the fault clears, or “LOCKOUT” and will 
not restart until the operator clears the fault using the 
keypad. If a system safety is in effect, the message will 
be displayed to the operator when the STATUS key is 
pressed.
LD10605
STATUS 
KEY
In some cases, a control panel fault will occur after 
a VSD fault, possibly during system shutdown or at 
some later time. This is known as an “ALL FAULT” 
and these faults will be recorded as such under the 
HISTORY information stored at the instant of the pri-
mary fault. In some cases, this information may be 
valuable in troubleshooting the primary fault. An ex-
ample of the “ALL FAULT” history message is shown 
on Page 263 under the HISTORY key. When an “ALL 
FAULT” occurs, associated history information will 
not be stored. If an additional fault does not occur, the 
“ALL FAULTS” display will indicate NONE. In cases 
where a VSD fault occurs during the rampdown of a 
control panel fault (i.e.: low suction pressure, low wa-
ter temp, etc.), the VSD fault will be stored as a new 
fault with the associated fault information stored at the 
instant the VSD fault occurred (i.e.: IGBT Gate Drive, 
Single Phase Input, VSD CT Plug, etc.). The control 
panel fault that occurred prior to the VSD fault will be 
stored with the associated complete data related to the 
fault as a numerically lower numbered history in the 
history buffers. 
High Discharge Pressure Cutout (Software) 
Fault
The High Discharge Pressure Cutout is a software 
fault. A system will fault and shut down with a con-
trolled ramped shutdown on high discharge pressure 
when the discharge pressure rises above 274 psig for 
0.5 seconds. The system will be allowed to restart 
when the discharge pressure falls to 259 psig. The sys-
tem will also be inhibited from starting if the pressure 
is above 259 psig. The fault message for this safety is 
shown below:
SYS  X  YYYYYYYY  HIGH  DISCHARGE  PRESSURE
X indicates the system and YYYYYYYY indicates 
the system is in a “FAULT” condition and will restart 
when the 120 second anti-recycle timer times out, or 
“LOCKOUT” and will not restart until the operator 
clears the fault using the keypad.