JOHNSON CONTROLS
313
SECTION 9 - MAINTENANCE
FORM 201.23-NM2
ISSUE DATE: 09/25/2020
9
TABLE 37 - PRESSURE TRANSDUCER OUTPUT VOLTAGE (MEASURED SIGNAL TO RETURN AT THE
TRANSDUCER)
SUCTION PRESSURE
TRANSDUCER
(125 PSIG)
DISCHARGE PRESSURE
TRANSDUCER
(275 PSIG)
DISCHARGE PRESSURE
TRANSDUCER
(275 PSIG)
PRESSURE VOLTAGE PRESSURE VOLTAGE PRESSURE VOLTAGE
0 0.50 0 0.50 140 2.54
5 0.66 5 0.57 145 2.61
10 0.82 10 0.65 150 2.68
15 0.98 15 0.72 155 2.75
20 1.14 20 0.79 160 2.83
25 1.30 25 0.86 165 2.90
30 1.46 30 0.94 170 2.97
35 1.62 35 1.01 175 3.05
40 1.78 40 1.08 180 3.12
45 1.94 45 1.15 185 3.19
50 2.10 50 1.23 190 3.26
55 2.26 55 1.30 195 3.34
60 2.42 60 1.37 200 3.41
65 2.58 65 1.45 205 3.48
70 2.74 70 1.52 210 3.55
75 2.90 75 1.59 215 3.63
80 3.06 80 1.66 220 3.70
85 3.22 85 1.74 225 3.77
90 3.38 90 1.81 230 3.85
95 3.54 95 1.88 235 3.92
100 3.70 100 1.95 240 3.99
105 3.86 105 2.03 245 4.06
110 4.02 110 2.10 250 4.14
115 4.18 115 2.17 255 4.21
120 4.34 120 2.25 260 4.28
125 4.50 125 2.32 265 4.35
130 2.39 270 4.43
135 2.46 275 4.50