JOHNSON CONTROLS
260
FORM 201.23-NM2 
ISSUE DATE: 09/25/2020
SECTION 8 - MICROPANEL
LD10605
PROGRAM 
KEY
PROGRAM KEY
Program Key Operation
Various operating parameters are programmable by the 
user. These are modified by pressing the PROGRAM 
key and then the  (ENTER) key to enter Program 
Mode. A listing of the limits of the programmable val-
ues is found below. Note that the Imperial units are ex-
act values, while Metric units are only approximate.
The  ▲  and  ▼  (ARROW) keys are used to scroll 
through the user programmable values. A value may be 
changed by keying in the new value and pressing the  
(ENTER) key to store the new value in memory. The 
cursor will be displayed on the screen when a number 
key is pressed. The first line of each message will indi-
cate the chiller default (DEF) value), lowest acceptable 
programmable value (LO), and highest acceptable pro-
grammable value (HI). The user programmable value 
is programmed on in the second line of the message.
When the PROGRAM key is first pressed, the follow-
ing display will appear indicating the user is in the pro-
gram mode:
PROGRAM  MODE  XXXX
 PRESS  ENTER  KEY  TO  CONTINUE
Pressing the  (ENTER) key again will display the 
first programmable selection.
Suction Pressure Cutout
PROGRAM     ◄DEF  XXXXX LO  XXXXX  HI  XXXXX
SUCTION  PRESSURE  CUTOUT     = XXX.X PSIG
The suction pressure cutout is protects the chiller from 
a low refrigerant condition. It also helps protect from 
a freeze-up due to low or no chilled liquid flow. How-
ever, it is only a back-up for a flow switch and cannot 
protect against an evaporator freeze under many condi-
tions. This cutout is programmable and should gener-
ally be programmed for 24 psig (1.65 barg) for chilled 
water cooling.
The cutout is programmable between 24.0 psig and 
36.0 psig (1.65 barg and 2.48 barg) in the Water Cool-
ing mode and 5.0 psig and 36.0 psig (0.34 barg and 
2.28 barg) in the Glycol Cooling mode. The default 
value for both modes will be 24.0 psig (1.65 barg).