JOHNSON CONTROLS
270
FORM 201.23-NM2 
ISSUE DATE: 09/25/2020
SECTION 8 - MICROPANEL
LD10605
MANUAL OVERRIDE
KEY
MANUAL OVERRIDE KEY
Manual Overrride Key Operation
If the MANUAL OVERRIDE key is pressed during 
a schedule shutdown, the STATUS display will dis-
play the message below. This indicates that the Daily 
Schedule is being ignored and the chiller will start 
when chilled liquid temperature allows, Remote Con-
tacts, UNIT switch and SYSTEM switches permitting. 
This is a priority message and cannot be overridden by 
anti-recycle messages, fault messages, etc. when in the 
STATUS display mode. Therefore, do not expect to see 
any other STATUS messages when in the MANUAL 
OVERRIDE mode. MANUAL OVERRIDE is to only 
be used in emergencies or for servicing. Manual over-
ride mode automatically disables itself after 30 min-
utes.
MANUAL OVERRIDE