SECTION 8 - MICROPANEL
FORM 201.23-NM2 
ISSUE DATE: 09/25/2020
8
UNIT DATA KEY
LD10605
UNIT DATA
KEY
General
The UNIT DATA key provides the user with displays 
of unit temperatures, and unit related data. Displays 
can be selected by repeatedly pressing the UNIT DATA 
key or the▲ or ▼ Arrow Keys.
Unit Data Key Operation
The first key press displays Evaporator Leaving and 
Return Chilled Liquid Temps.
UNIT  CHILLED  LIQUID  LEAVING = XXX.X °F
           ENTERING = XXX.X °F
The next key press of the UNIT DATA key or the ▼ 
(ARROW) key displays the ambient air temperature.
UNIT
   OUTSIDE  AMBIENT  AIR  TEMP = XXX.X °F
The next key press will display the time remaining on 
the load and unload timers.
UNIT    LOAD TIMER = XXX SEC
         UNLOAD  TIMER = XXX SEC
The next key press displays the error in temperature 
between the actual leaving chilled liquid temperature 
and the setpoint temperature. The display also shows 
the rate of change of the chilled liquid temperature.
UNIT             TEMP ERROR = XXX.X °F
                             RATE = XXX.X °F/M
The next key press displays the system designated as 
the lead system and the Flow Switch status (ON or 
OFF).
UNIT     LEAD  SYSTEM  NUMBER = X
      FLOW SWITCH = XXX 
The next key press displays the status of the evapora-
tor pump and heater, where XXX is either ON or OFF.
UNIT   EVAP PUMP RUN = XXX
                 EVAP HEATER = XXX