CHILLED LIQUID AND SUCTION TEMPERATURE SENSOR INPUT VOLTAGE
TABLE 35 - TEMPERATURE INPUT VOLTAGE SENSOR (MEASURED SIGNAL TO SHIELD AT THE SENSOR)
TEMP. (ºF) VOLTAGE TEMP. (ºF) VOLTAGE TEMP. (ºF) VOLTAGE
16.1 1.52 35.9 2.19 55.6 2.85
16.7 1.54 36.5 2.21 56.3 2.87
17.3 1.56 37.0 2.23 56.9 2.89
17.9 1.58 37.6 2.25 57.5 2.91
18.5 1.60 38.2 2.27 58.1 2.93
19.1 1.62 38.7 2.29 58.7 2.95
19.7 1.64 39.3 2.30 59.4 2.97
20.3 1.66 39.9 2.32 60.0 2.99
20.9 1.68 40.4 2.34 60.6 3.01
21.5 1.70 41.0 2.36 61.3 3.03
22.1 1.72 41.6 2.38 61.9 3.05
22.7 1.74 42.1 2.40 62.5 3.07
23.3 1.76 42.7 2.42 63.2 3.09
23.9 1.78 43.3 2.44 63.8 3.11
24.5 1.80 43.9 2.46 64.5 3.13
25.0 1.82 44.4 2.48 65.1 3.14
25.6 1.84 45.0 2.50 65.8 3.16
26.2 1.86 45.6 2.52 66.5 3.18
26.8 1.88 46.2 2.54 67.1 3.20
27.3 1.90 46.7 2.56 67.8 3.22
27.9 1.91 47.3 2.58 68.5 3.24
28.5 1.93 47.9 2.60 69.2 3.26
29.0 1.95 48.5 2.62 69.9 3.28
29.6 1.97 49.1 2.64 70.6 3.30
30.2 1.99 49.7 2.66 71.3 3.32
30.8 2.01 50.3 2.68 72.0 3.34
31.3 2.03 50.8 2.70 72.7 3.36
31.9 2.05 51.4 2.71 73.4 3.38
32.5 2.07 52.0 2.73 74.2 3.40
33.0 2.09 52.6 2.75 74.9 3.42
33.6 2.11 53.2 2.77
34.2 2.13 53.8 2.79
34.8 2.15 54.5 2.81
35.3 2.17 55.0 2.83