EasyManua.ls Logo

York YCIV Series - Page 158

York YCIV Series
326 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
JOHNSON CONTROLS
158
FORM 201.23-NM2
ISSUE DATE: 09/25/2020
SECTION 6 - TECHNICAL DATA
ND-X NEOPRENE ISOLATOR SPECIFICATIONS
Installation of Neoprene Mounts
It is not necessary to bolt the mountings to a concrete
pad in most cases. Mountings should always be bolted
to the chiller rails. When mountings and the chiller are
ENGLISH
SIZE D H L T W BC CS MBD
ND-C 2 9/16 2 3/4 5 1/2 1/4 2 5/16 4 1/8 1/2-13x1" 1/2"
ND-D 3 3/8 2 3/4 6 1/4 5/16 4 5 1/2-13x1" 1/2"
ND-DS 3 3/8 2 3/4 6 1/4 5/16 4 5 1/2-13x1" 1/2"
SI
ND-C 65.1 69.9 139.7 6.4 58.7 101.9 1/2-13x1" 13
ND-D 85.7 69.9 158.8 7.9 101.6 127.0 1/2-13x1" 13
ND-DS 85.7 69.9 158.8 7.9 101.6 127.0 1/2-13x1" 13
PIN 54 = N
**WEIGHT RANGE (LB) **WEIGHT RANGE (KG) COLOR YORK P/N YORK P/N
Up to 751 Up to 341 ND-C Yellow 029-24584-001
751–1651 341–749 ND-D Yellow 029-24584-002
1651–3226 749–1463 ND-E Yellow 029-24584-003
** Value is de-rated by 15%
UNITS SHIPPED BEFORE JUNE 15, 2008
installed on steel framing above the ground, the mount-
ings should be bolted to the steel framework. Lower
the chiller on to the mountings evenly to avoid placing
excessive weight on individual isolators.
"CS" Cap Screw
BC
"MBD" Max. Bolt Dia.
Steel Plate - Top
&
Bottom Neoprene
covered to prevent
corrosion
L
T
H
W
D
LD10569
Steel Plate - Top &
Bottom. Neoprene
covered to prevent
corosion.
“CS” CAP SCREW
“MBD” MAXIUM
BOLT DIAMETER
D
H
W
T
BC
L

Table of Contents