SECTION 8 - MICROPANEL
FORM 201.23-NM2
ISSUE DATE: 09/25/2020
8
Remote Temperature Reset Selection
Remote temperature reset from an external source may
be tied directly into the chiller microprocessor board.
OPTIONS REMOTE TEMP RESET INPUT
XXXXXXXXXXXXXXXXXX
Selections may be made for DISABLED (no signal), 0
VDC to10 VDC, 2 VDC to 10 VDC, 0 mA to 20 mA,
and 4 mA to 20 mA.
OPTIONS REMOTE TEMP RESET INPUT
DISABLED
OPTIONS REMOTE TEMP RESET INPUT
◄ ► 0.0 TO 10.0 VOLTS DC
OPTIONS REMOTE TEMP RESET INPUT
◄ ► 2.0 TO 10.0 VOLTS DC
OPTIONS REMOTE TEMP RESET INPUT
◄ ► 0.0 TO 20.0 MILLIAMPS
OPTIONS REMOTE TEMP RESET INPUT
◄ ► 4.0 TO 20.0 MILLIAMPS
The default setting for Remote Temp Reset is DIS-
ABLED. This display will only appear if the remote
temp limit option is enabled at the factory.
Remote Current Limit Input Selection
Remote current limit from an external source may be
tied directly into the chiller microprocessor board.
OPTIONS REMOTE CURRENT LIMIT INPUT
XXXXXXXXXXXXXXXXXXXXX
Selections may be made for DISABLED (no signal), 0
VDC to 10 VDC, 2 VDC to 10 VDC, 0 mA to 20 mA,
and 4 mA to 20 mA.
OPTIONS REMOTE CURRENT LIMIT INPUT
DISABLED
OPTIONS REMOTE CURRENT LIMIT INPUT
◄ ► 0.0 TO 10.0 VOLTS DC
OPTIONS REMOTE CURRENT LIMIT INPUT
◄ ► 2.0 TO 10 VOLTS DC
OPTIONS REMOTE CURRENT LIMIT INPUT
◄ ► 0.0 TO 20.0 MILLIAMPS
OPTIONS REMOTE CURRENT LIMIT INPUT
◄ ► 4.0 TO 20.0 MILLIAMPS
The default setting for Remote Current Reset is DIS-
ABLED. This display will only appear if the remote
current limit option is enabled at the factory.
Remote Sound Limit Selection
Remote sound limit from an external source may be
tied directly into the chiller microprocessor board.
OPTIONS REMOTE SOUND LIMIT INPUT
XXXXXXXXXXXXXXXXXXXX
Selections may be made for DISABLED (no signal), 0
VDC to10 VDC, 2 VDC to 10 VDC, 0 mA to 20 mA,
and 4 mA to 20 mA.
OPTIONS REMOTE SOUND LIMIT INPUT
DISABLED
OPTIONS REMOTE SOUND LIMIT INPUT
◄ ► 0.0 TO 10.0 VOLTS DC
OPTIONS REMOTE SOUND LIMIT INPUT
◄ ► 2.0 TO 10.0 VOLTS DC
OPTIONS REMOTE SOUND LIMIT INPUT
◄ ► 0.0 TO 20.0 MILLIAMPS
OPTIONS REMOTE SOUND LIMIT INPUT
◄ ► 4.0 TO 20.0 MILLIAMPS
The default setting for Remote Sound Limit is DIS-
ABLED. This display will only appear if the remote
sound limit option is enabled at the factory.
Low Ambient Cutout Enable/Disable
The low ambient cutout may be enabled or disabled.
When enabled, the chiller will cut off when the low
ambient cutout is reached. When disabled, the chiller
will run at any temperature.
OPTIONS LOW AMBIENT TEMPERATURE CUTOUT
◄ ► ENABLED
OPTIONS LOW AMBIENT TEMPERATURE CUTOUT
◄ ► DISABLED
The default setting for the low ambient cutout will be
ENABLED.