JOHNSON CONTROLS
296
FORM 201.23-NM2
ISSUE DATE: 09/25/2020
SECTION 8 - MICROPANEL
8/25/2014
ENG
POINT LIST CODE: S = STANDARD O = OPTIONAL N = NOT AVAILABLE PAGE
Address Scale Imper SI
POINT LIST DESCRIPTION 12345678910REF
P43
BV12
YT2_ S01_ P43 nvoYTS01p043 SNVT_switch (95)
BD 12
0072 N/A Sys 2 Economizer Solenoid Valve Status
SSSSSSSS
P43
P44
BV13
YT2_ S01_ P44 nvoYTS01p044 SNVT_switch (95)
BD 13 0073 N/A P44
P45
BV14
YT2_ S01_ P45 nvoYTS01p045 SNVT_switch (95)
BD 14 0074 N/A P45
P46
BV15
YT2_ S01_ P46 nvoYTS01p046 SNVT_switch (95)
BD 15 0075 N/A P46
P47
BV16
YT2_ S01_ P47 nvoYTS01p047 SNVT_switch (95)
BD 16 0076 N/A P47
P48
BV17
YT2_ S01_ P48 nvoYTS01p048 SNVT_switch (95)
BD 17 0077 N/A P48
P49
BV18
YT2_ S01_ P49 nvoYTS01p049 SNVT_switch (95)
BD 18 0078 N/A P49
P50
BV19
YT2_ S01_ P50 nvoYTS01p050 SNVT_switch (95)
BD 19 0079 N/A 0 / 1 0 / 1 S1-1 Cooling Type: 0=Water, 1=Glycol SSSSSSSS P50
P51
BV20
YT2_ S01_ P51 nvoYTS01p051 SNVT_switch (95)
BD 20 0080 N/A 0 / 1 0 / 1 Local/Remote Control Mode: 0 = Local, 1 = Remote S S S S S S S S P51
P52
BV21
YT2_ S01_ P52 nvoYTS01p052 SNVT_switch (95)
BD 21 0081 N/A 0 / 1 0 / 1 Display Units Mode: 0 = Imperial, 1 = SI SSSSSSSS P52
P53
BV22
YT2_ S01_ P53 nvoYTS01p053 SNVT_switch (95)
BD 22 0082 N/A P53
P54
BV23
YT2_ S01_ P54 nvoYTS01p054 SNVT_switch (95)
BD 23 0083 N/A P54
P55
BV24
YT2_ S01_ P55 nvoYTS01p055 SNVT_switch (95)
BD 24 0084 N/A P55
P56
MV1
YT2_ S01_ P56 nvoYTS01p056 SNVT_count_f (51)
ADI 1 0030 X 1 enum enum *Sys 1 Operational Code SSSSSSSS P56
P57
MV2
YT2_ S01_ P57 nvoYTS01p057 SNVT_count_f (51)
ADI 2 0031 X 1 enum enum *Sys 1 Fault Code SSSSSSSS P57
P58
MV3
YT2_ S01_ P58 nvoYTS01p058 SNVT_count_f (51)
ADI 3 0032 X 1 enum enum *Sys 2 Operational Code SSSSSSSS P58
P59
MV4
YT2_ S01_ P59 nvoYTS01p059 SNVT_count_f (51)
ADI 4 0033 X 1 enum enum *Sys 2 Fault Code SSSSSSSS P59
P60
MV5
YT2_ S01_ P60 nvoYTS01p060 SNVT_count_f (51)
ADI 5 0034 X 1 % % Sys 1 Flash Tank Level (%) SSSSSSSS P60
P61
MV6
YT2_ S01_ P61 nvoYTS01p061 SNVT_count_f (51)
ADI 6 0035 X 1 count count Sys 1 Condenser Fan Stages Running (0-7) SSSSSSSS P61
P62
MV7
YT2_ S01_ P62 nvoYTS01p062 SNVT_count_f (51)
ADI 7 0036 X 1 count count Sys 2 Flash Tank Level (%) SSSSSSSS P62
P63
MV8
YT2_ S01_ P63 nvoYTS01p063 SNVT_count_f (51)
ADI 8 0037 X 1 count count Sys 2 Condenser Fan Stages Running (0-7) SSSSSSSS P63
P64
MV9
YT2_ S01_ P64 nvoYTS01p064 SNVT_count_f (51)
ADI 9 0038 X 1 count count Lead System Number SSSSSSSS P64
P65
MV10
YT2_ S01_ P65 nvoYTS01p065 SNVT_count_f (51)
ADI 10 0039 X 1 enum enum Sys 1 & 2 Debug Code ( internal use only) NNNNNNNN P65
P66
AV30
YT2_ S01_ P66 nvoYTS01p066 SNVT_count_f (51)
ADF 30 0040 X 1 °F °C Local Leaving Chilled Liquid Setpoint SSSSSSSS P66
P67
AV31
YT2_ S01_ P67 nvoYTS01p067 SNVT_count_f (51)
ADF 31 0041 X 1 °F °C Low Leaving Chilled Liquid Temp Cutout SSSSSSSS P67
P68
AV32
YT2_ S01_ P68 nvoYTS01p068 SNVT_count_f (51)
ADF 32 0042 X 1 % % Sys 1 Flash Tank Drain Valve % Open SSSSSSSS P68
P69
AV33
YT2_ S01_ P69 nvoYTS01p069 SNVT_count_f (51)
ADF 33 0043 X 1 % % Sys 2 Flash Tank Drain Valve % Open SSSSSSSS P69
P70
AV34
YT2_ S01_ P70 nvoYTS01p070 SNVT_count_f (51)
ADF 34 0044 X 10 PSI BAR Low Suction Pressure Cutout SSSSSSSS P70
P71
AV35
YT2_ S01_ P71 nvoYTS01p071 SNVT_count_f (51)
ADF 35 0045 X1 * volts volts VSD DC Bus Voltage SSSSSSSS P71
P72
AV36
YT2_ S01_ P72 nvoYTS01p072 SNVT_count_f (51)
ADF 36 0046 X1 *
°F °C Remote Leaving Chilled Liquid Setpoint N N N N N N S S P7
2
P73
AV37
YT2_ S01_ P73 nvoYTS01p073 SNVT_count_f (51)
ADF 37 0047 X1 * °F °C Sys 1 Suction Superheat SSSSSSSS P73
P74
AV38
YT2_ S01_ P74 nvoYTS01p074 SNVT_count_f (51)
ADF 38 0048 X1 * °F °C Cooling Range SSSSSSSS P74
P75
AV39
YT2_ S01_ P75 nvoYTS01p075 SNVT_count_f (51)
ADF 39 0049 X1 * °F °C Sys 1 Discharge Superheat SSSSSSSS P75
P76
AV40
YT2_ S01_ P76 nvoYTS01p076 SNVT_count_f (51)
ADF 40 0050 X 1 °F °C Sys 2 Suction Temperature SSSSSSSS P76
P77
AV41
YT2_ S01_ P77 nvoYTS01p077 SNVT_count_f (51)
ADF 41 0051 X 1 °F °C Sys 2 Discharge Temperature SSSSSSSS P77
P78
AV42
YT2_ S01_ P78 nvoYTS01p078 SNVT_count_f (51)
ADF 42 0052 X 1 °F °C Sys 2 Suction Superheat SSSSSSSS P78
P79
AV 43
YT2_ S01_ P79 nvoYTS01p079 SNVT_count_f (51)
ADF 43 0053 X 1 °F °C Sys 2 Discharge Superheat SSSSSSSS P79
P80
BV25
YT2_ S01_ P80 nvoYTS01p080 SNVT_switch (95)
BD 25 0085 N/A 0/1 0/1 Sys 1 Lockout NNSSSSSS P80
P81
BV26
YT2_ S01_ P81 nvoYTS01p081 SNVT_switch (95)
BD 26 0086 N/A 0/1 0/1 Sys 2 Lockout NNSSSSSS P81
P82
BV27
YT2_ S01_ P82 nvoYTS01p082 SNVT_switch (95)
BD 27 0087 N/A P82
P83
BV28
YT2_ S01_ P83 nvoYTS01p083 SNVT_switch (95)
BD 28 0088 N/A P83
P84
BV29
YT2_ S01_ P84 nvoYTS01p084 SNVT_switch (95)
BD 29 0089 N/A P84
2
4
5
6
7
8
9
10
NOTE: The Appropriate Product Code Listing Summary Should Accompany Document
BACnet Engineering Units shown with an (*) Asterisk will be assigned a BACnet En
g Unit type of (95) ie NO UNITS.
Status Codes: Special Display characters such as (, ), [, ], {, },/,
\,%,< and > are not compatible with Elink N2 formats. Substitute text strings , "-", PCT, GTN will be used .
Status Codes: Status Code Text string lengths are limited to 60 tot
al characters (including spaces)
MODBUS ENG UNITS
1
3
see note 3
N2
Metasys
LON SNVT Type
ENG
PAGE
Ref
BACnet
Object
Typ/Ins
Bacnet Object
Name
LON Profile
Name
NOTES
LON SNVTS Used: SNVT_count (8), SNVT_lev_percent (81), SNVT_temp_
p (105), SNVT_switch (95) , SNVT_time_minute (123) , SNVT_freq_hz (76) , SNVT_amp (01) , SNVT_elec_kwh (13) , SNVT_power_kilo (83) ,
SNVT_volt (44) , SNVT_volt_ac (138), SNVT_press_p (87)
MODBUS scaling factors indicated in BOLD with an (*) aste
risk are User Configurable, by a field technician if necessary. All Modbus values are of the type SIGNED with the exception of the User Configurabale values that are all
UNSIGNED. Modbus Function Types Supported
(ENG P03-P06 = Types 03, 06, 16) , ( ENG P07- P10 = 01, 03, 05, 15, 06, 16), (ENG P11-P35, P56-P79) = 03, 04) , (ENG P36-P55, P80 -P84 = 01, 02, 03)
Revision: YCAV_YCIV BAS (Rev K_03g).xlsx Tab: YCAV a
nd YCIV Property of Johnson Controls, York, PA Page: 2