SECTION 8 - MICROPANEL
FORM 201.23-NM2
ISSUE DATE: 09/25/2020
8
TABLE 33 - YORKTALK 2 COMMUNICATIONS DATA MAP (CONT’D)
Imperial
SI
Point List Description
1
2
3
4
5
6
7
8
9
10
83 VSD_DCB_V_24 AI75 588
03,04 x1 ADF 79 Volts Volts VSD DC Bus Voltage Sys 2/4 S
84 REM_SETPOINT AI76 589
03,04
x10 ADF 80 °F °C Remote Leaving Chilled Liquid Setpoint
S
85 S1_SUC_SHEAT AI77 590
03,04 x10 ADF 81 °F (diff) °C (diff) Sys 1 Suction Superheat S
86 S2_SUC_SHEAT AI78 591
03,04 x10 ADF 82 °F (diff) °C (diff) Sys 2 Suction Superheat S
87 S3_SUC_SHEAT AI79 592
03,04 x10 ADF 83 °F (diff) °C (diff) Sys 3 Suction Superheat S
88 S4_SUC_SHEAT AI80 593
03,04 x10 ADF 84 °F (diff) °C (diff) Sys 4 Suction Superheat S
89 COOLING_RNG AI81 594
03,04 x10 ADF 85 °F °C Cooling Range S
90 S1_DSC_SHEAT AI82 595
03,04 x10 ADF 86 °F (diff) °C (diff) Sys 1 Discharge Superheat S
91 S2_DSC_SHEAT AI83 596
03,04 x10 ADF 87 °F (diff) °C (diff) Sys 2 Discharge Superheat S
92 S3_DSC_SHEAT AI84 597
03,04 x10 ADF 88 °F (diff) °C (diff) Sys 3 Discharge Superheat S
93 S4_DSC_SHEAT AI85 598
03,04 x10 ADF 89 °F (diff) °C (diff) Sys 4 Discharge Superheat S
94 S1_SYS_STATE AI86 599
03,04 x1 ADF 90 None None
Sys 1 System State [0=Stopped, 1=Running, 2=Faulted,
4=Locked Out, 5=Pre-Run
S
95 S2_SYS_STATE AI87 600
03,04 x1 ADF 91 None None
Sys 2 System State [0=Stopped, 1=Running, 2=Faulted,
4=Locked Out, 5=Pre-Run
S
96 S3_SYS_STATE AI88 601
03,04 x1 ADF 92 None None
Sys 3 System State [0=Stopped, 1=Running, 2=Faulted,
4=Locked Out, 5=Pre-Run
S
97 S4_SYS_STATE AI89 602
03,04 x1 ADF 93 None None
Sys 4 System State [0=Stopped, 1=Running, 2=Faulted,
4=Locked Out, 5=Pre-Run
S
98 S1_MTR_OVER AI90 603
03,04 x1 ADF 94 Amps Amps Sys 1 Motor Current Overload Setting S
99 S2_MTR_OVER AI91 604
03,04 x1 ADF 95 Amps Amps Sys 2 Motor Current Overload Setting S
100 S3_MTR_OVER AI92 605
03,04 x1 ADF 96 Amps Amps Sys 3 Motor Current Overload Setting S
101 S4_MTR_OVER AI93 606
03,04 x1 ADF 97 Amps Amps Sys 4 Motor Current Overload Setting S
102 S13_ALARM BI1 1282
01,02,03 N/A BD5 0/1 0/1 Sys 1/3 Alarm [0=No Alarm, 1=Alarm] S
103 S24_ALARM BI2 1283
01,02,03 N/A BD6 0/1 0/1 Sys 2/4 Alarm [0=No Alarm, 1=Alarm] S
104 EVAP_HEATER BI3 1284
01,02,03 N/A BD7 0/1 0/1 Evaporator Heater Status S
105 EVAP_PUMP BI4 1285
01,02,03 N/A BD8 0/1 0/1 Evaporator Pump Status S
106 S1_COMP_RUN BI5 1286
01,02,03 N/A BD9 0/1 0/1 Sys 1 Compressor Run Status S
107 S2_COMP_RUN BI6 1287
01,02,03 N/A BD10 0/1 0/1 Sys 2 Compressor Run Status S
108 S3_COMP_RUN BI7 1288
01,02,03 N/A BD11 0/1 0/1 Sys 3 Compressor Run Status S
109 S4_COMP_RUN BI8 1289
01,02,03 N/A BD12 0/1 0/1 Sys 4 Compressor Run Status S
110 S1_ECON_SV BI9 1290
01,02,03 N/A BD13 0/1 0/1 Sys 1 Economizer Solenoid Valve Status S
111 S2_ECON_SV BI10 1291
01,02,03 N/A BD14 0/1 0/1 Sys 2 Economizer Solenoid Valve Status S
112 S3_ECON_SV BI11 1292
01,02,03 N/A BD15 0/1 0/1 Sys 3 Economizer Solenoid Valve Status S
113 S4_ECON_SV BI12 1293
01,02,03 N/A BD16 0/1 0/1 Sys 4 Economizer Solenoid Valve Status S
114 WATER_GLYCOL BI13 1294
01,02,03 N/A BD17 0/1 0/1 Cooling Type [0=Water, 1=Glycol] S
115 LOCAL_REMOTE BI14 1295
01,02,03 N/A BD18 0/1 0/1 Local Remote Control Mode [0=Local, 1=Remote] S
116 DISP_UNITS BI15 1296
01,02,03 N/A BD19 0/1 0/1 Display Units [0=Imperial, 1=SI] S
1
2
3
4
5
6
7
8
9
10
BACnet
Object
Instance
Modbus
Address
Modbus Data Type
Supported
Modbus
Scaling
(See
Note 5)
N2 Metasys
Engineering Units Point List Code: S = Standard O = Optional N = Not Available
Item
Ref
Num
BACnet Name
BINARY READ ONLY POINTS
NOTES
Units have Native BACnet MS/TP, Modbus RTU, and N2 communications. No external Gateway is required for these interfaces unless the customer is using Connected Services.
BACnet Object Types: 0 = Analog In, 1 = Analog Out, 2 = Analog Value, 3 = Binary In, 4 = Binary Out, 8 = Device, 15 = Alarm Notification (0-127 are reserved ASHRAE Objects)
WC = Inches of water Column, CFM = Cubic Feet per Minute, FPM = Feet Per Minute, PSI = Pounds per Square Inch, Pa = Pascals, kPa = kiloPascals, PPM = Parts Per Million, kJ/kg = kiloJoules per kilogram
Values that are not applicable due to unit configuration and options will be sent as zero (0).
Modbus values are all of type signed. Scaling values in
x10
(Bold) indicate scaling in metric is x100. Scaling and signing may not be modified in the field.
YCAV
and YCIV Native
Property of Johnson Controls, Inc.
Subject to change without notice.
3 of 4
02/17/2017