SECTION 8 - MICROPANEL
FORM 201.23-NM2
ISSUE DATE: 09/25/2020
8
TABLE 33 - YORKTALK 2 COMMUNICATIONS DATA MAP (CONT’D)
03,04 x1 ADF 79 Volts Volts VSD DC Bus Voltage Sys 2/4 S
03,04
x10 ADF 80 °F °C Remote Leaving Chilled Liquid Setpoint
S
03,04 x10 ADF 81 °F (diff) °C (diff) Sys 1 Suction Superheat S
03,04 x10 ADF 82 °F (diff) °C (diff) Sys 2 Suction Superheat S
03,04 x10 ADF 83 °F (diff) °C (diff) Sys 3 Suction Superheat S
03,04 x10 ADF 84 °F (diff) °C (diff) Sys 4 Suction Superheat S
03,04 x10 ADF 85 °F °C Cooling Range S
03,04 x10 ADF 86 °F (diff) °C (diff) Sys 1 Discharge Superheat S
03,04 x10 ADF 87 °F (diff) °C (diff) Sys 2 Discharge Superheat S
03,04 x10 ADF 88 °F (diff) °C (diff) Sys 3 Discharge Superheat S
03,04 x10 ADF 89 °F (diff) °C (diff) Sys 4 Discharge Superheat S
03,04 x1 ADF 90 None None
Sys 1 System State [0=Stopped, 1=Running, 2=Faulted,
4=Locked Out, 5=Pre-Run
S
03,04 x1 ADF 91 None None
Sys 2 System State [0=Stopped, 1=Running, 2=Faulted,
4=Locked Out, 5=Pre-Run
S
03,04 x1 ADF 92 None None
Sys 3 System State [0=Stopped, 1=Running, 2=Faulted,
4=Locked Out, 5=Pre-Run
S
03,04 x1 ADF 93 None None
Sys 4 System State [0=Stopped, 1=Running, 2=Faulted,
4=Locked Out, 5=Pre-Run
S
03,04 x1 ADF 94 Amps Amps Sys 1 Motor Current Overload Setting S
03,04 x1 ADF 95 Amps Amps Sys 2 Motor Current Overload Setting S
03,04 x1 ADF 96 Amps Amps Sys 3 Motor Current Overload Setting S
03,04 x1 ADF 97 Amps Amps Sys 4 Motor Current Overload Setting S
01,02,03 N/A BD5 0/1 0/1 Sys 1/3 Alarm [0=No Alarm, 1=Alarm] S
01,02,03 N/A BD6 0/1 0/1 Sys 2/4 Alarm [0=No Alarm, 1=Alarm] S
01,02,03 N/A BD7 0/1 0/1 Evaporator Heater Status S
01,02,03 N/A BD8 0/1 0/1 Evaporator Pump Status S
01,02,03 N/A BD9 0/1 0/1 Sys 1 Compressor Run Status S
01,02,03 N/A BD10 0/1 0/1 Sys 2 Compressor Run Status S
01,02,03 N/A BD11 0/1 0/1 Sys 3 Compressor Run Status S
01,02,03 N/A BD12 0/1 0/1 Sys 4 Compressor Run Status S
01,02,03 N/A BD13 0/1 0/1 Sys 1 Economizer Solenoid Valve Status S
01,02,03 N/A BD14 0/1 0/1 Sys 2 Economizer Solenoid Valve Status S
01,02,03 N/A BD15 0/1 0/1 Sys 3 Economizer Solenoid Valve Status S
01,02,03 N/A BD16 0/1 0/1 Sys 4 Economizer Solenoid Valve Status S
114 WATER_GLYCOL BI13 1294
01,02,03 N/A BD17 0/1 0/1 Cooling Type [0=Water, 1=Glycol] S
115 LOCAL_REMOTE BI14 1295
01,02,03 N/A BD18 0/1 0/1 Local Remote Control Mode [0=Local, 1=Remote] S
01,02,03 N/A BD19 0/1 0/1 Display Units [0=Imperial, 1=SI] S
1
2
3
4
5
6
7
8
9
10
Object
Instance
Modbus
Address
Modbus Data Type
Supported
Modbus
Scaling
Note 5)
N2 Metasys
Engineering Units Point List Code: S = Standard O = Optional N = Not Available
Ref
Num
NOTES
Units have Native BACnet MS/TP, Modbus RTU, and N2 communications. No external Gateway is required for these interfaces unless the customer is using Connected Services.
BACnet Object Types: 0 = Analog In, 1 = Analog Out, 2 = Analog Value, 3 = Binary In, 4 = Binary Out, 8 = Device, 15 = Alarm Notification (0-127 are reserved ASHRAE Objects)
WC = Inches of water Column, CFM = Cubic Feet per Minute, FPM = Feet Per Minute, PSI = Pounds per Square Inch, Pa = Pascals, kPa = kiloPascals, PPM = Parts Per Million, kJ/kg = kiloJoules per kilogram
Values that are not applicable due to unit configuration and options will be sent as zero (0).
Modbus values are all of type signed. Scaling values in
x10
(Bold) indicate scaling in metric is x100. Scaling and signing may not be modified in the field.
YCAV
and YCIV Native
Property of Johnson Controls, Inc.
Subject to change without notice.