SECTION 6 - TECHNICAL DATA
WATER TEMPERATURE AND FLOWS
(ENGLISH UNITS)
MODEL NUM-
BER
YCIV
LEAVING WATER
TEMPERATURE (°F)
COOLER FLOW
(GPM)
AIR ON CONDENSER (°F)
MIN.
1
MAX.
2
MIN. MAX. MIN. MAX
0157(S/P/H) 40 60 140 675 0 125
0157(E/V) 40 60 160 750 0 125
0177(S/P/H) 40 60 160 750 0 125
0177(E/V) 40 60 160 750 0 125
0187(S/P/H) 40 60 160 750 0 125
0187(E/V) 40 60 160 750 0 125
0197(E/V) 40 60 180 750 0 125
0207(S/P/H) 40 60 180 800 0 125
0207(E/V) 40 60 180 750 0 125
0227(S/P/H) 40 60 180 800 0 125
0227(E/V) 40 60 180 750 0 125
0247(S/P/H) 40 60 180 800 0 125
0247(E/V) 40 60 180 800 0 125
0267(S/P/H) 40 60 180 800 0 125
0267(E/V) 40 60 250 1200 0 125
0287(S/P/H) 40 60 250 1200 0 125
0287(E/V) 40 60 250 1200 0 125
0307(S/P/H) 40 60 300 1200 0 125
0327(E/V) 40 60 300 1200 0 125
0357(S/P/H) 40 60 300 1200 0 125
0357(E/V) 40 60 300 1200 0 125
0397(S/P/H) 40 60 300 1200 0 125
NOTES:
1. For leaving brine temperature below 40°F (4.4°C), contact your nearest Johnson Controls o󰀩ce for application requirements.
2. For leaving water temperature higher than 60°F (15.6°C), contact the nearest Johnson Controls o󰀩ce for application guidelines.