JOHNSON CONTROLS
73
SECTION 6 - TECHNICAL DATA
FORM 201.23-NM2
ISSUE DATE: 09/25/2020
6
YCIV
E/V
CONTROL
KVA (7)
UNIT SHORT CIRCUIT WITH-
STAND (KA)
FIELD WIRING & PROTECTION
FIELD WIRING & PROTECTION
STD. & ULTRA QUIET COND. FANS HIGH HEAD/HIGH STATIC FANS TWO-SPEED COND. FANS
TERMINAL
BLOCK (STD)
CIRCUIT
BREAKER
(OPT)
MINI-
MUM CKT.
AMPACITY
(MCA) (3)
RECOMMEND-
ED FUSE/CKT.
BREAKER RAT-
ING (4)
MAX. IN-
VERSE TIME
CKT. BRKR.
RATING (2)
MAX DUAL
ELEMENT
FUSE
SIZE (2)
MINIMUM
CKT.
AMPACITY
(MCA) (3)
RECOMMENDED
FUSE/CKT.
BREAKER RAT-
ING (4)
MAX.
INVERSE
TIME CKT.
BRKR. RAT-
ING (2)
MAX DUAL
ELEMENT
FUSE
SIZE (2)
MINIMUM
CKT.
AMPACITY
(MCA) (3)
RECOMMENDED
FUSE/CKT.
BREAKER RAT-
ING (4)
MAX.
INVERSE
TIME CKT.
BRKR.
RATING (2)
MAX DUAL
ELEMENT
FUSE
SIZE (2)
0157
1.8 30 65 270 300 350 350
1.8 30 65 341 400 450 450
388 450 500 500
0177
1.8 30 65 288 350 400 400
1.8 30 65 365 450 500 500
417 500 500 500
0187
1.8 30 65 325 400 450 450
1.8 30 65 411 500 600 600
469 600 600 600
0197
1.8 30 65 345 400 450 450
1.8 30 65 437 500 600 600
495 600 600 600
0207
1.8 30 65 362 450 500 500
1.8 30 65 458 600 600 600
522 600 700 700
0227
1.8 30 65 371 450 500 500
1.8 30 65 469 600 600 600
539 600 700 700
0247
1.8 30 65 424 500 600 600
1.8 30 65 536 700 700 700
606 700 800 800
See page 92 for Electrical Data footnotes.
HIGH EFFICIENCY YCIV_ _ _ _ E/V HIGH EFFICIENCY YCIV_ _ _ _ E/V
MODEL NO./NAME-
PLATE
SYSTEM 1
SYSTEM 2
STD. & ULTRA QUIET
COND. FANS
HIGH HEAD/STATIC
COND. FANS
TWO-SPEED
COND. FANS
STD. & ULTRA QUIET COND. FANS HIGH HEAD/STATIC COND. FANS TWO-SPEED COND. FANS
YCIV
E/V
INPUT
VOLTS
(9)
INPUT
FREQ
COMPRESSOR
CONDENSER
FANS
COMPRESSOR
CONDENSER
FANS
COMPRESSOR
CONDENSER
FANS
COMPRESSOR
CONDENSER
FANS
COMPRESSOR
CONDENSER
FANS
COMPRESSOR
CONDENSER
FANS
RLA (5) QTY.
FLA
(EA)
RLA (5) QTY.
FLA
(EA)
RLA (5) QTY.
FLA
(EA)
RLA (5) QTY.
FLA
(EA)
RLA (5) QTY.
FLA
(EA)
RLA (5) QTY.
FLA
(EA)
0157
460 60 110 4 2.8
110 4 2.8
380 60 139 4 3.5 139 4 9.3 139 4 3.5 139 4 9.3
0177
460 60 111 5 2.8
122 4 2.8
380 60 141 5 3.5 141 5 9.3 154 4 3.5 154 4 9.3
0187
460 60 154 5 2.8
105 5 2.8
380 60 195 5 3.5 195 5 9.3 132 5 3.5 132 5 9.3
0197
460 60 141 5 2.8
141 5 2.8
380 60 179 5 3.5 179 5 9.3 179 5 3.5 179 5 9.3
0207
460 60 141 6 2.8
152 5 2.8
380 60 179 6 3.5 179 6 9.3 193 5 3.5 193 5 9.3
0227
460 60 150 6 2.8
150 6 2.8
380 60 190 6 3.5 190 6 9.3 190 6 3.5 190 6 9.3
0247
460 60 194 6 2.8
149 6 2.8
380 60 245 6 3.5 245 6 9.3 188 6 3.5 188 6 9.3
HIGH EFFICIENCY 2-COMPRESSOR UNITS (CONT'D)
One Field Provided Power Supply Circuit. Field Connections to Factory provided
Terminal Block (Standard); or Individual System Breakers (Optional).