Handbook Ucontrol type-lines PXDM Date 06/04
TBL02_55-GB06/04 Part.-No. 00153239-GB
Page 82 / 105
10.1.2 Adjustment analog output A
With the attitudes A min and A max the characteristic of the output voltage can be adapted
Factory setting: A min = 0 V, A max = 10 V
Setting range: A min = 0-5 V, A max = 10-5 V
With the attitudes A Inverting
the output voltage can bei inverted
Factory setting OFF
↓ ↑
↓ ↑
Analog out
Inverting OFF
(factory setting)
A max: 10-5 V
A min: 0-5 V
10 V
5 V
U Motor , inputsignal, modulation, Group
control, second controller
Inverting ON
min: 0-5 V
A max: 10-5 V
10 V
5 V
Analog out
U Motor , input signal, modulation, group
control, second controller