30  266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER  |  OI/266CXX/MODBUS-EN REV. A   
 
… 6  Installation 
… Mounting recommendations 
 
Fill level measurement on the steam boiler  
(drum water level) 
 
H High pressure side 
L  Low pressure side 
1 Gas 
2 Liquid 
3 Condensate vessel 
Figure 22:  Level measurement on the steam boiler 
 
•  Mount the transmitter at the same height or below the 
lowest level to be measured. 
•  Connect the high pressure side ‘+’ of the transmitter to the 
bottom of the tank. 
•  The low pressure side ‘–’ of the transmitter up at the tank. 
Above the maximum level, connect using a condensate 
vessel. 
•  Use the condensate vessel to ensure that the impulse line of 
the low pressure side is always filled with liquid (condensate) 
at a constant height. 
 
 
 
 
 
 
Temperature measurement 
 
•  Mount the temperature sensor in the downstream pipe of 
the primary element. 
•  Consider the downstream straight pipe requirements. 
•  If there is a significant difference between the temperature 
of the measuring medium and the ambient temperature, the 
measuring error caused by heat conduction must be 
minimized by insulating the installation location accordingly. 
•  Use class ‘A’ sensors to maximize accuracy. 
•  The lengths of the protective tubes should be 15 to 20 times 
the diameter of the protective tube for gas measurements 
and 3 to 5 times the diameter of the protective tube for 
liquid measurements.