266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A 75
Application of the Diagnosis Main and Main 2 Registers
The 266CRH / 266CRT, 266CSH / 266CST has two ‘Diagnosis’
(Diagnosis Main and Main 2). The Diagnosis Main register
(Address 411, 412) each containing 16 bits.
The Diagnosis Main 2 register (Address 413) containing 16 bits.
Each bit represents an error.
The registers are structured as follows:
M11191
411 412 414
= true (1) = false (0)
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Figure 3: Diagnosis Main Register (Example, 16-bit Register)
The bit position is assigned to the errors in accordance with the
’Bit’ column in the table Diagnosis codes.
The following assignment applies to the example in Figure 3:
Register / Bit Fault message
411
Bit 3
Process temperature out of range
411
Bit 5
Differential pressure sensor out of range
414
Bit 2
Multivariable input out of range
Diagnosis codes
Register
Address
Bit Error
411 0
1
2 Fourth sensor out of range
3 Process temperature out of range
4 Static pressure sensor out of range
5 Differential pressure sensor out of range
6
7
8 Process temperature out of limits
9 Sensor temperature out of limit
10 Static pressure sensor out of limits
11 Differential pressure sensor out of limits
12 Process temperature sensor fail
13 Sensor temperature fail
14 Static pressure sensor fail
15 Differential pressure sensor fail
Diagnosis codes
Register
Address
Bit Error
412 0 Maximum working pressure exceeded
1 Input simulation active
2
3
4
5 Non-Volatile checking active
6 Non-Volatile storage active
7 Non-Volatile memory burn error
8 Memory failure
9
10
11 Electronic Interface communication error
12 Electronic Interface error
13 Non-Volatile memory burn error
14 Sensor memory fail
15 Sensor invalid
414 0 Wrong flow direction
1 Multivariable input invalid
2 Multivariable input out of range
3
4 Multivariable calculation out of range
5 Replace info
6 Electronic temperature error
7 Electronic diagnosis alarm
8 Changed operating conditions
9 PILD output
10 Configuration error
11 Electronic diagnosis warning
12
13
14
15 Pressure overrange

Table of Contents

Other manuals for ABB 266CSH

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB 266CSH and is the answer not in the manual?

ABB 266CSH Specifications

General IconGeneral
BrandABB
Model266CSH
CategoryTransmitter
LanguageEnglish

Related product manuals