ACH580 Installation, Operation and Maintenance Manual 101
ACH580 E-Clipse Bypass
Box enclosure terminals maximum wire size and terminal torque values
Type Code
1
Nominal Output
Ratings
Frame
Size
Maximum Wire Size and Terminal Torque
Drive
Current
Package
Power
Circuit
Breaker
Disconnect
Switch
Motor
Termination
Ground
Lugs
AHP
575 Volts
2
ACH580-VxR-02A7-6 2.7 2 R2
#10
62 in-lbs
#10
55 in-lbs
#6
11-13 in-lbs
#4
35 in-lbs
ACH580-VxR-03A9-6 3.9 3 R2
ACH580-VxR-06A1-6 6.1 5 R2
ACH580-VxR-09A0-6 9 7.5 R2
ACH580-VxR-011A-6 11 10 R2
ACH580-VxR-017A-6 17 15 R2
#6
55 in-lbs
ACH580-VxR-022A-6 22 20 R3
#1
35 in-lbs
#2
50 in-lbs
ACH580-VxR-027A-6 27 25 R3
#4
55 in-lbs
ACH580-VxR-032A-6 32 30 R3
1) “VxR” represents both VCR and VDR.
2) VCR is rated 600Y/347V. For use on a solidly grounded Wye source only.
Type Code
1
Nominal Output
Ratings
Base
Drive
Frame
Size
Maximum Wire Size and Terminal Torque
Drive
Current
Package
Power
Circuit
Breaker
UL
(NEMA)
Type
1 and 12
Circuit
Breaker
UL
(NEMA)
Type 3R
Disconnec
t Switch
UL (NEMA)
Type
1 and 12
Disconnect
Switch
UL (NEMA)
Type 3R
Motor
Terminals
UL (NEMA)
Type
1 and 2
Motor
Terminals
UL (NEMA)
Type 3R
Ground
Lugs
UL
(NEMA)
Type
1 and 2
Ground
Lugs
UL
(NEMA)
Type 3R
AHP
208/230 Volts
ACH580-BxR-04A6-2 4.6 1 R1
#12
62 in-lbs
#12
62 in-lbs
#10
55 in-lbs
#10
55 in-lbs
#6
11-13 in-lbs
#6
11-13 in-lbs
#4
35 in-lbs
#4
35 in-lbs
ACH580-BxR-06A6-2 6.6 1.5 R1
ACH580-BxR-07A5-2 7.5 2 R1
ACH580-BxR-10A6-2 10.6 3 R1
ACH580-BxR-017A-2 16.7 5 R1
#8
62 in-lbs
#8
62 in-lbs
#6
55 in-lbs
#6
55 in-lbs
ACH580-BxR-024A-2 24.2 7.5 R2
ACH580-BxR-031A-2 30.8 10 R2
#6
62 in-lbs
#6
62 in-lbs
#4
55 in-lbs
#4
55 in-lbs
#1
35 in-lbs
#1
35 in-lbs
#2
50 in-lbs
#2
50 in-lbs
ACH580-BxR-046A-2 46.2 15 R3
#2
62 in-lbs
#2
62 in-lbs
#2
55 in-lbs
#2
55 in-lbs
#2/0
110 in-lbs
#2/0
110 in-lbs
ACH580-BxR-059A-2 59.4 20 R3
#1
55 in-lbs
#1
55 in-lbs
ACH580-BxR-075A-2 74.8 25 R4
#1/0
75 in-lbs
#1/0
75 in-lbs
ACH580-BxR-088A-2 88 30 R5
#1/0
124 in-lbs
Consult
factory
#2/0
275 in-lbs
Consult
factory
#2/0
71 in-lbs
Consult
factory
#1/0
50 in-lbs
Consult
factory
ACH580-BxR-114A-2 114 40 R6
#4/0
275 in-lbs
300 MCM
301 in-lbs
ACH580-BxR-143A-2 143 50 R6
#3/0
124 in-lbs
300 MCM
275 in-lbs
500 MCM
372 in-lbs
ACH580-BxR-169A-2 169 60 R7
ACH580-BxR-211A-2 211 75 R7 373
MCM
274 in-lbs
2 X 500
MCM
274 in-lbs
2 X 500
MCM
372 in-lbs
ACH580-BxR-248A-2 248 100
2
R8
1) “BxR” represents both BCR and BDR.
2) 100 HP @ 230V.