68 ACH580 Installation, Operation and Maintenance Manual
ACH580-01 Installation
Fault messages
Code
(hex)
Fault / Aux. code Cause What to do
1080 Backup/Restore timeout Panel or PC tool has
failed to communicate
with the drive when
backup was being
made or restored.
Request backup or restore again.
1081 Rating ID fault Drive software has not
been able to read the
rating ID of the drive.
Reset the fault to make the drive try to
reread the rating ID.
If the fault reappears, cycle the power
to the drive. You may have to be
repeat this. If the fault persists,
contact your local ABB representative.
2310 Overcurrent Output current has
exceeded internal fault
limit.
In addition to an actual
overcurrent situation,
this fault may also be
caused by an earth
fault or supply phase
loss.
Check motor load.
Check acceleration times in
parameter group 23 Speed reference
ramp (speed control) or 28 Frequency
reference chain (frequency control).
Also check parameters 46.01 Speed
scaling, 46.02 Frequency scaling and
46.03 Torque scaling.
Check motor and motor cable
(including phasing and delta/star
connection).
Check there are no contactors
opening and closing in motor cable.
Check that the start-up data in
parameter group 99 corresponds to
the motor rating plate.
Check that there are no power factor
correction capacitors or surge
absorbers in motor cable.
Check for an earth fault in motor or
motor cables by measuring the
insulation resistances of motor and
motor cable. See Checking the
insulation of the assembly on
page 16.
2330 Earth leakage
Programmable fault: 31.20
Earth fault
Drive has detected load
unbalance typically due
to earth fault in motor
or motor cable.
Check there are no power factor
correction capacitors or surge
absorbers in motor cable.
Check for an earth fault in motor or
motor cables by measuring the
insulation resistances of motor and
motor cable.
Try running the motor in scalar control
mode if allowed. (See parameter
99.04 Motor control mode.)
If no earth fault can be detected,
contact your local ABB representative.