50 ACH580 Installation, Operation and Maintenance Manual
ACH580-01 Installation
2. Complete commissioning
Default configurations — HVAC and PID Control
For more information on Default configurations, see pages 39, 40 and 44.
Note: You can adjust Process PI(D) in the PID control
submenu of the Primary Settings menu after you have
commissioned the drive to use PID control.
1
Press the Hand key to start the motor. The Home view is
shown on the panel. Select Menu (press on the soft key
under “Menu”).
2 From the Main menu, select Primary settings.
3 Select Start, stop, reference and How do you control?
4
The default configurations are shown on the panel.
For HVAC, press Direct control via I/O.
For PID Control, press PID control, single motor.