40 ACH580 Installation, Operation and Maintenance Manual
ACH580-01 Installation
Default control connections for the PID control, single motor
 
Terminal sizes:
1. R1…R5: 24…14 AWG (0.2…2.5 mm
2
): Terminals +24V, DGND, DCOM, B+, A-, DGND, Ext. 24V
2. 26…16 AWG (0.14…1.5 mm
2
): Terminals DI, AI, AO, AGND, RO, STO
3. R6…R9: 26...14 AWG (0.14…2.5 mm
2
) (all terminals)
4. Tightening torques: 0.4 lb-ft (0.5…0.6 N•m)
PID control, single motor
Input signals Output signals
• Setpoint selected from: control panel setpoint/constant 
setpoint /analog input (AI1)
• Analog output AO1: Output frequency
• PID feedback (AI2) • Analog output AO2: Motor current
• Start/stop selection (DI1) • Relay output 1: Damper control
• Constant speed/frequency selection (DI3) • Relay output 2: Running
• Start interlock 1 (DI4) • Relay output 3: Fault (-1)
1) Connected with jumpers at the factory.
2) Only frames R6…R9 have terminals 40 and 41 for external 24 V AC/DC input.
X1  Reference voltage and analog inputs and outputs
1 SCR Signal cable shield (screen)
2 AI1 Analog input 1
3 AGND Analog input circuit common
4 +10V Reference voltage 10 V DC
5 AI2 Actual feedback: 0 to 20 mA
6 AGND Analog input circuit common
7 AO1 Output frequency:  0 to 10 V
8 AO2 Motor current:   0 to 20 mA
9 AGND Analog output circuit common
X2 & X3   Aux. voltage output and programmable digital inputs
10 +24V Aux. voltage output +24 V DC, max. 250 mA
11 DGND Aux. voltage output common
12 DCOM Digital input common for all
13 DI1 Stop (0)/Start (1) 
1
4 DI2 Not configured
15 DI3 Constant frequency/speed selection
16 DI4 Start interlock 1 (1 = allow start)
17 DI5 Not configured
18 DI6 Not configured
X6, X7, X8 Relay outputs
19 RO1C
Damper control
250 V AC / 30 V DC
2 A
20 RO1A
21 RO1B
22 RO2C
Running
250 V AC / 30 V DC 
2 A
23 RO2A
24 RO2B
25 RO3C
Fault (-1)
250 V AC / 30 V DC
2 A
26 RO3A
27 RO3B
X5 Embedded eldbus
29 B+
Embedded eldbus, EFB (EIA-485)
30 A-
31 DGND
S4 TERM Termination switch
S5 BIAS Bias resistors switch
X4 Safe torque o
34 OUT1
Safe torque o
35 OUT2
36 SGND
37 IN1
38 IN2
+10 V
+24 V
+
-
4…20 mA temp.
feedback signal
Start/Stop signal
Safety
Run status
Fault status
Energize damper
19 connected to 21
Running
22 connected to 24
Fault condition
25 connected to 26