ACH580 Installation, Operation and Maintenance Manual 21
ACH580-01 Installation
Control cable terminal and lead-through data
Imperial control cable lead-throughs, wire sizes and tightening torques (T) are given 
below.
Metric control cable lead-throughs, wire sizes and tightening torques (T) are given 
below.
Frame 
size
Cable 
lead-throughs
Control cable entries and terminal sizes
Holes
Max 
cable 
size
+24V, DCOM, DGND, EXT. 24V
terminals
DI, AI/O, AGND, RO, STO 
terminals
Wire size T Wire size T
pcs in. AWG lbΒ·ft AWG lbΒ·ft
R1 3 0.67 24β¦14 0.4 26β¦14 0.4
R2 3 0.67 24β¦14 0.4 26β¦14 0.4
R3 3 0.67 24β¦14 0.4 26β¦14 0.4
R4 4 0.67 24β¦14 0.4 26β¦14 0.4
R5 3 0.67 24β¦14 0.4 26β¦14 0.4
R6 4 0.67 26β¦14 0.4 26β¦14 0.4
R7 4 0.67 26β¦14 0.4 26β¦14 0.4
R8 4 0.67 26β¦14 0.4 26β¦14 0.4
R9 4 0.67 26β¦14 0.4 26β¦14 0.4
Frame 
size
Cable 
lead-throughs
Control cable entries and terminal sizes
Holes
Max 
cable 
size
+24V, DCOM, DGND, EXT. 24V
terminals
DI, AI/O, AGND, RO, STO 
terminals
Wire size T Wire size T
pcs mm mm
2
NΒ·m mm
2
NΒ·m
R1 3 17 0.2β¦2.5 0.5β¦0.6 0.14β¦1.5 0.5β¦0.6
R2 3 17 0.2β¦2.5 0.5β¦0.6 0.14β¦1.5 0.5β¦0.6
R3 3 17 0.2β¦2.5 0.5β¦0.6 0.14β¦1.5 0.5β¦0.6
R4 4 17 0.2β¦2.5 0.5β¦0.6 0.14β¦1.5 0.5β¦0.6
R5 3 17 0.2β¦2.5 0.5β¦0.6 0.14β¦1.5 0.5β¦0.6
R6 4 17 0.14β¦2.5 0.5β¦0.6 0.14β¦2.5 0.5β¦0.6
R7 4 17 0.14β¦2.5 0.5β¦0.6 0.14β¦2.5 0.5β¦0.6
R8 4 17 0.14β¦2.5 0.5β¦0.6 0.14β¦2.5 0.5β¦0.6
R9 4 17 0.14β¦2.5 0.5β¦0.6 0.14β¦2.5 0.5β¦0.6