EasyManua.ls Logo

ABB ACH580 Series - Basic Control Connections for E-Clipse HVAC Default; Parameters Changed Relative to E-Clipse HVAC Default

ABB ACH580 Series
156 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
108 ACH580 Installation, Operation and Maintenance Manual
ACH580 E-Clipse Bypass
Basic control connections for E-Clipse HVAC Default
Parameters Changed Relative to E-Clipse HVAC Default
* Smoke Control (Override1) is a fixed input. Closing Digital Input 6 will place the E-Clipse Bypass in Smoke Control mode which may
reassign the function of the other Digital Inputs. Refer to the Smoke Control (Override1) documentation.
Parameter Number Description Setting
1
X2
+24Vdc
2
+24Vdc
3
Digital Input Common
4
GND
5
Digital Input 1 (Parameter 1601) START/STOP
6
Digital Input 2 (Parameter 1602,06) NOT SEL
7
Digital Input 3 (Parameter 1603) START INTERLOCK 1
8
Digital Input 4 (Parameter 1604,07) NOT SEL
9
Digital Input 5
(Parameter 1605, 1701)
NOT SEL
Digital Input 6 (Fixed)
SMOKE CONTROL*
(OVERRIDE 1)
10
11
X2
12
13
14
15
16
17
18
19
20
21
22
23
24
25
Relay Output 1 (parameter 1401) BYP NOT FLT
Default Operation: Bypass Not Faulted 11 connected to 13
Bypass Faulted 11 connected to 12
Relay Output 2 (parameter 1404) SYS RUNNING
Default Operation: System Running 14 connected to 16
Relay Output 3 (parameter 1407) SYS STARTED
Default Operation: System started 17 connected to 19
Relay Output 4 (parameter 1410) BYPASS SEL
Default Operation: Bypass selected 20 connected to 22
Relay Output 5 (parameter 1413) BYPASS AUTO
Default Operation: Bypass auto 23 connected to 25
1
2
3
4
5
6
7
8
9
Terminal for Signal Cable Shield
Analog Input 1
Analog Input Common
+10V Reference Voltage for Potentiometer
Analog Input 2
Analog Input Common
Analog Output 1
Analog Output 2
Analog Output Common
ACH580 CONTROL BOARD
E-CLIPSE BYPASS CONTROL BOARD
X1
+
-

Table of Contents

Other manuals for ABB ACH580 Series

Related product manuals