14 ACH580 Installation, Operation and Maintenance Manual
ACH580-01 Installation
Installing the drive vertically, frames R6…R9
1. Mark the hole locations for the six mounting holes using the mounting temp
late
include
d in the package. Do not leave the mounting template under the drive.
The drive dimensions and hole locations are also shown in the drawings in t
he
ACH580 Hard
ware manual, publication number 3AXD50000044839.
Note: You can use only two bolts instead of four to attach the lower part of the drive.
2. Drill the mounting holes.
3. Insert anchors or plugs into the holes and start the bolts into the anchors or plugs.
Use a sufficient number of bolts that are long enough to make them carry the
weight
of
the drive.
4. Position the drive onto the bolts on the wall. Lift the drive with a lifting de
vice with
anoth
er person as it is heavy.
5. Tighten the top two bolts in the wall securely
.
c
a
d
e
b
R6 R7 R8 R9
in. mm in. mm in. mm. in. mm
a 22.5 571 24.5 623 27.6 701 28.3 718
b 20.9 531 23.0 583 25.9 658 25.9 658
c 8.4 213 9.7 245 10.4 263 13.6 345
d 11.8 300 11.8 300 11.8 300 11.8 300
e 6.1 155 6.1 155 6.1 155 7.9 200
IP21,
UL (NEMA)
Type 1
lb kg lb kg lb kg lb kg
93.5 42.4 119.1 54.0 152.2 69.0 213.9 97.0
IP55,
UL (NEMA)
Type 12
lb kg lb kg lb kg lb kg
94.8 43.0 123.5 56.0 169.8 77.0 227.1 103.0
1
× 4
3
× 2 × 2
4
2
5
M8
R6…R9: M8 (5/16 in)