1. Check free space requirements
The drive must be installed on the wall. There are two alternative ways to install it.
Frame
size
Vertical installation - Free space
Above (a)
1)
Below (b)
2)
Beside
(c)
3)
mm in mm in mm in
R1 200 7.87 150 5.91 150 5.91
R2 200 7.87 150 5.91 150 5.91
R3 200 7.87 200 7.87 150 5.91
R4 53 2.09 200 7.87 150 5.91
R5 100 3.94 200 7.87 150 5.91
R6 155 6.10 300 11.81 150 5.91
R7 155 6.10 300 11.81 150 5.91
R8 155 6.10 300 11.81 150 5.91
R9 200 7.87 300 11.81 150 5.91
3AXD00000586715.xls K
1) Free space above is measured from the frame, not from the hood used
in UL (NEMA) Type 12 frames.
Note: The height of the hood for frames R4 and R9 exceeds the
requirement of free space above for these frames..
2) Free space below is measured from the frame, not from the cable box
used in frames R1…R2 and R5…R9.
3) Free space between the drive and other objects, e.g. wall.