ACH580 Installation, Operation and Maintenance Manual 129
ACH580 E-Clipse Bypass
Warning listing
The following table lists the warnings by code number and describes each.
Warning 
Code
Warning Name In 
Panel
Warning Possible Cause Corrective Action
4001 INP PHASE A 
LOSS
Warning will occur in 
drive mode. In bypass, 
warning will occur if 
bypass contactor has 
not closed. Unit will trip 
on Fault 3010 if the 
bypass contactor is 
closed
Loose J8 connector
Loose wiring on 
Contactor assembly.
Blown upstream fuse
Check J8 connector
Check yellow wire on 
input block
Check incoming 
voltage, phase to 
ground
4002 INP PHASE B 
LOSS
Warning will occur in 
drive mode. In bypass, 
warning will occur if 
bypass contactor has 
not closed. Unit will trip 
on Fault 3011 if the 
bypass contactor is 
closed
Loose J8 connector
Loose wiring on 
Contactor assembly.
Blown upstream fuse
Check J8 connector
Check black wire on 
input block
Check incoming 
voltage, phase to 
ground
4003 INP PHASE C 
LOSS
Warning will occur in 
drive mode. In bypass, 
warning will occur if 
bypass contactor has 
not closed. Unit will trip 
on Fault 3012 if the 
bypass contactor is 
closed
Loose J8 connector
Loose wiring on 
Contactor assembly.
Blown upstream fuse
Check J8 connector
Check red wire on input 
block
Check incoming 
voltage, phase to 
ground
4004 AUTO TRANSFER Message is displayed 
when the drive faults 
and the bypass 
switches to bypass 
mode as configured in 
Parameter 1608
Drive fault Check drive
4005 EXT COMM ERR Time between fieldbus 
messages has 
exceeded timeout 
interval set with 
parameter 3005
Incorrect 
Communication 
settings in Group 51 
& 53.
Poor Connections
Noise on 
Communication Line
Check Group 51 & 58
Tighten Connections
Check Communication 
Cable Grounding
4006 Selected by PAR 
1620:
PERMISSIVE
DAMPER END 
SWITCH
VALVE OPENING
PRE-LUBE CYCLE
Warning will occur 
when start order is 
given and the 
“Permissive” is not 
present
Permissive condition 
is not satisfied.
Bad 24v supply
Bad digital input
Check 24 Volts on 
RBCU unit
Check for 24 volts on 
respective DI when 
condition is satisfied
Check Parameter 0103 
for status of digital input
4007 PCB TEMP RBCU unit reached 
181 degrees 
Fahrenheit, 83 degrees 
Celsius
Cabinet cooling has 
failed
Ambient conditions 
too high
Bad RBCU unit
Stop drive and let cool 
down and restart
Add additional cooling
Replace RBCU