130 ACH580 Installation, Operation and Maintenance Manual
ACH580 E-Clipse Bypass
4008 DRIVE SETUP Warning generated
when configuration of
drive is such that
bypass can not
properly control the
drive. Specifically, drive
parameters 10.01,
10.02, 16.01, 16.08
Incorrect parameters
settings
Check that drive
parameter 95.21, bit 5
= “Bypass present”
4009 BYPASS RUN
DELAY
Warning is generated
when a bypass start
command is issued and
there is non zero time
value in bypass
parameter 1614
NA NA
4010 MTR OVERLOAD Bypass warning if
motor overload
conditions exist as
defined in the drive
Drive Mode:
Bad Motor
Bad CTs
Bad RBCU
Bypass mode:
Bad motor
Bad CTs
Bad RBCU
Either mode:
low input voltage
Drive Mode:
Refer to ACH580
manual for proper
troubleshooting
techniques
Bypass Mode:
Check that J2
connector is firmly
seated in RBCU
Check input voltage
Does overload
condition exist?
4011 MTR UNDERLOAD Warning comes at half
the time of a mtr
underload fault. See
fault 3017 for further
text
NA Parameter 3002 is the
time
Parameter 3003 is the
level
4012 BYPASS
DISABLED
Warning will be
generated if parameter
1613 is set to “Disable”
NA NA
4013 DRIVE LINK
ERROR
Same as Fault 3019
however will occur
when not in supervisory
mode
Bad cable between
drive and bypass
Drive parameter
95.21, bit 5 not set
for “Bypass present”
Proper seating of cable
in drive and RBCU
(connector J3)
Check that drive
parameter 95.21, bit 5
= “Bypass present”
Follow DriveLink
recovery procedure
4014 DRIVE TEST Warning is generated
when bypass
parameter 1617 is set
to “enable”
NA NA
4015 START DRIVE 1ST Message displayed on
initial “out of box”
power up sequence
NA Run drive in Hand
Warning
Code
Warning Name In
Panel
Warning Possible Cause Corrective Action