150 ACH580 Installation, Operation and Maintenance Manual
ACH580-PCR/PDR
Maintenance
Maintenance intervals 
If installed in an appropriate environment, the drive requires very little maintenance. 
This table lists the routine maintenance intervals recommended by ABB for ACH580 
enclosures in addition to the intervals on page 81. 
Enclosure air filter replacement B3 – UL (NEMA) Type 12 hinged door 
wall mount enclosures
Filter material
This procedure applies to drive with input disconnect configurations in UL (NEMA) 
Type 12 hinged door wall mount enclosures. This filter is located at the bottom of the 
enclosure. Use the following procedure to check and replace filters.
1. On the enclosure, remove the screws holding the filter bracket in place.
2. Remove the filter kit from the enclosure.
3. Lift the filter out of the filter bracket and replace as appropriate.
4. With the filter in the filter bracket, reinstall filter kit onto enclosure.
5. Replace the mounting screws. Tighten to the recommended torque of 2 N•m 
(1.47 ft-lbs) per installation instruction 3AXD50000221370.
Diagnostics
Refer to the Diagnostics instructions on page 57.
Maintenance Configuration Interval Instruction
Check/replace hinged 
door wall mount 
enclosure inlet air filter
Hinged door wall 
mount UL (NEMA) 
Type 12 enclosures
Check every 3 
months. Replace 
as needed.
Enclosure air filter replacement 
B3 – UL (NEMA) Type 12 hinged 
door wall mount enclosures on 
page 150.
Material Filter Type
American Air Filter (358-35-06A-12A)
POLYKLEON WHITE 12.7mm (1/2 in.) X 152.4mm (6 in.) X 
304.6mm (12 in.) stk.
Mounting 
Screws (4X)
Filter Bracket
Back of 
Enclosure
Enclosure Door
Bottom of Enclosure