ACH580 Installation, Operation and Maintenance Manual 39
ACH580-01 Installation
Default control connections for the HVAC default
Terminal sizes:
1. R1…R5: 24…14 AWG (0.2…2.5 mm
2
): Terminals +24V, DGND, DCOM, B+, A-, DGND, Ext. 24V
2. 26…16 AWG (0.14…1.5 mm
2
): Terminals DI, AI, AO, AGND, RO, STO
3. R6…R9: 26...14 AWG (0.14…2.5 mm
2
) (all terminals)
4. Tightening torques: 0.4 lb-ft (0.5…0.6 N•m)
HVAC default direct I/O control
Input Signals Output signals
• Analog frequency/speed reference (AI1) • Analog output AO1: Output frequency
• Start/stop selection (DI1) • Analog output AO2: Motor current
• Constant speed/frequency selection (DI3) • Relay output 1: Damper control
• Start interlock 1 (DI4) • Relay output 2: Running
• Relay output 3: Fault (-1)
Notes:
1) Ground the outer shield of the cable 360 degrees under the grounding clamp on the grounding shelf for
the control cables.
2) Connected with jumpers at the factory.
3) Only frames R6…R11 have terminals 40 and 41 for external 24 V AC/DC input.
X1 Reference voltage and analog inputs and outputs
1 SCR Signal cable shield (screen)
2 AI1 Output frequency/speed reference: 0 to 10 V
3 AGND Analog input circuit common
4 +10V Reference voltage 10 V DC
5 AI2 Actual feedback: 0 to 20 mA
6 AGND Analog input circuit common
7 AO1 Output frequency: 0 to 10 V
8 AO2 Motor current: 0 to 20 mA
9 AGND Analog output circuit common
X2 & X3 Aux. voltage output and programmable digital inputs
10 +24V Aux. voltage output +24 V DC, max. 250 mA
11 DGND Aux. voltage output common
12 DCOM
Digital input common for all
13 DI1 Stop (0)/Start (1)
14 DI2 Not configured
15 DI3 Constant frequency/speed selection
16 DI4 Start interlock 1 (1 = allow start)
17 DI5 Not configured
18 DI6 Not configured
X6, X7, X8 Relay outputs
19 RO1C
Damper control
250 V AC / 30 V DC
2 A
20 RO1A
21 RO1B
22 RO2C
Running
250 V AC / 30 V DC
2 A
23 RO2A
24 RO2B
25 RO3C
Fault (-1)
250 V AC / 30 V DC
2 A
26 RO3A
27 RO3B
X5 Embedded eldbus
29 B+
Embedded eldbus, EFB (EIA-485)
30 A-
31 DGND
S4 TERM Termination switch
S5 BIAS Bias resistors switch
X4 Safe torque o
34 OUT1
Safe torque o
35 OUT2
36 SGND
37 IN1
38 IN2
+10 V
+24 V
+
-
0...10 V DC speed
reference signal
Start/Stop signal
Safety
Run status
Fault status
Energize damper
19 connected to 21
Running
22 connected to 24
Fault condition
25 connected to 26