ACH580 Installation, Operation and Maintenance Manual 49
ACH580-01 Installation
8
Check that the motor data is correct. Values are
predefined on the basis of the drive size but you should
verify that they correspond to the motor.
Start with the motor type.
Go to the edit view of a selected row by pressing .
Scroll the view with and .
Motor nominal cos Φ and nominal torque are optional.
Press (Next) to continue.
9
To change a value in an edit view:
Use and to move the cursor left and right.
Use and to change the value.
Press (Save) to accept the new setting, or press
(Cancel) to go back to the previous view without
making changes.
10
This step is optional, and requires rotating the motor. Do
not do this if it could cause any risk, or if the mechanical
setup does not allow it.
To do the direction test, select Spin the motor and press
(Next).
11 Press the Hand key on the panel to start the drive.
12
Check the direction of the motor.
If it is forward, select Yes, motor is spinning forward
and press (Next) to continue.
If the direction is not forward, select No, fix direction and
press (Next) to continue.
13
The first start is now complete and the drive is ready for
use.
Press (Done) to enter the Home view.