ACH580 Installation, Operation and Maintenance Manual 127
ACH580 E-Clipse Bypass
3037 PCB TEMP RBCU unit has reached
190 degrees Fahrenheit,
88 degrees Celsius
Cabinet cooling has
failed
Ambient conditions too
high
Bad RBCU unit
Stop drive and let cool
down and restart
Add additional cooling
Replace RBCU
3038 NO DRIVE DATA No drive data available Bypass not able to
extract drive data on
initial power up due to:
Bad cable/connection
between drive and
bypass.
Drive parameter 95.21,
bit 5 not set for
“Bypass present”
Proper seating of cable
in drive and RBCU
(connector J3)
Check that drive
parameter 95.21, bit 5 =
“Bypass present”
Check drive Group 58
Follow DriveLink
recovery procedure then
cycle power to bypass.
3039 FBA PAR CONF Non embedded fieldbus
has detected an error in
Group 51 parameters
Incorrect settings in
Group 51
Verify Group 51
parameters
3101 SFLASH CORRUPT Internal checksum error NA Cycle power
Replace RBCU
Upgrade firmware
3102 PMAP FILE Parameter file is corrupt Cycle Power
Contact ABB with
information that
preceded fault
3201 T1 OVERLOAD T1 program cycle is
overloaded
NA Contact ABB with
information that
proceeded fault
Cycle Power
Replace RBCU
3202 T2 OVERLOAD T2 program cycle is
overloaded
NA Contact ABB with
information that
proceeded fault
Cycle Power
Replace RBCU
3203 T3 OVERLOAD T3 program cycle is
overloaded
NA Contact ABB with
information that
proceeded fault
Cycle Power
Replace RBCU
3204 STACK OVERFLOW Program cycle is
overloaded
NA Contact ABB with
information that
proceeded fault
Cycle Power
Replace RBCU
3205 UNKNOWN CB Bypass control board
type is unknown.
NA Contact ABB with
information that
proceeded fault
3206 UNKNOWN DRIVE Drive reports rating not
found in bypass
software
Drive does not match
drives configured in
bypass RBCU
Replace RBCU or
reload with most current
firmware
Fault
Code
Fault Name In
Panel
Fault Possible Cause Corrective Action