32 ACH580 Installation, Operation and Maintenance Manual
ACH580-01 Installation
WARNING! To avoid danger or damage to the drive on IT systems and corner
grounded TN systems, see section Checking the compatibility with IT (ungrounded)
and corner-grounded TN systems (North America) on page 17.
Power wiring torque table
Frame size
R3
lb-ft N•m
T1/U, T2/V, T3/W 2.6 3.5
L1, L2, L3 2.6 3.5
R+, R- 2.6 3.5
PE Ground 1.1 1.5
BREAKERSINPUT
PE
MOTOR
R-
R+
UDC+
W/3TV/2TU/1T3L2L1L
BREAKERSINPUT
PE
MOTOR
R-
R+
UDC+
W/3TV/2TU/1T3L2L1L
R3
Typical Type 1
12
VAR
Power (Green) and
Fault (Red) LEDs
1
8
8
1
Option Mounting
Digital
Inputs
Analog Inputs
and Outputs
6
7
5
EMC