60 ACH580 Installation, Operation and Maintenance Manual
ACH580-01 Installation
A582 Auxiliary fan missing An auxiliary cooling fan
(IP55 internal fan) is
stuck or disconnected.
Check the auxiliary code.
Check the auxiliary fan and
connection.
Replace faulty fan.
Make sure the front cover of the drive
is in place and tightened. If the
commissioning of the drive requires
that the cover is off, this warning will
be generated even if the
corresponding fault is defeated. See
fault 5081 Auxiliary fan broken on
page 71.
A5A0 Safe torque off
Programmable warning:
31.22 STO indication run/
stop
Safe torque off function
is active, ie safety
circuit signal(s)
connected to connector
STO is lost.
Check safety circuit connections. For
more information, chapter The Safe
torque off function in the Hardware
manual of the drive and description of
parameter 31.22 STO indication run/
stop in the Firmware manual.
Check the value of parameter 95.04
Control board supply.
A5EA Measurement circuit
temperature
Problem with internal
temperature
measurement of the
drive.
Contact your local ABB
representative.
A5EB PU board powerfail Power unit power
supply failure.
Contact your local ABB
representative.
A5ED Measurement circuit ADC Measurement circuit
fault.
Contact your local ABB
representative.
A5EE Measurement circuit DFF Measurement circuit
fault.
Contact your local ABB
representative.
A5EF PU state feedback State feedback from
output phases does not
match control signals.
Contact your local ABB
representative.
A5F0 Charging feedback Charging feedback
signal missing.
Check the feedback signal coming
from the charging system.
A682 Flash erase speed
exceeded
The flash memory (in
the memory unit) has
been erased too
frequently,
compromising the
lifetime of the memory.
Avoid forcing unnecessary parameter
saves by parameter 96.07 or cyclic
parameter writes (such as user logger
triggering through parameters).
Check the auxiliary code (format
XYYY YZZZ). “X” specifies the source
of warning (1: generic flash erase
supervision). “ZZZ” specifies the flash
subsector number that generated the
warning.
A6A4 Motor nominal value The motor parameters
are set incorrectly.
Check the auxiliary code. See actions
for each code below.
The drive is not
dimensioned correctly.
Code
(hex)
Warning / Aux. code Cause What to do