72 ACH580 Installation, Operation and Maintenance Manual
ACH580-01 Installation
5693 Measurement circuit DFF Measurement circuit
fault.
Contact your local ABB
representative.
5696 PU state feedback State feedback from
output phases does not
match control signals.
Contact your local ABB
representative.
5697 Charging feedback Charging feedback
signal missing.
Check the feedback signal coming
from the charging system.
5698 Unknown PU fault The power unit logic
has generated a fault
which is not known by
the software.
Check the logic and software
compatibility.
6181 FPGA version
incompatible
Firmware and FPGA
versions are
incompatible.
Reboot the control unit (using
parameter 96.08 Control board boot)
or by cycling power. If the problem
persists, contact your local ABB
representative.
6306 FBA A mapping file Fieldbus adapter A
mapping file read error.
Contact your local ABB
representative.
6481 Task overload Internal fault. Reboot the control unit (using
parameter 96.08 Control board boot)
or by cycling power. If the problem
persists, contact your local ABB
representative.
6487 Stack overflow Internal fault. Reboot the control unit (using
parameter 96.08 Control board boot)
or by cycling power. If the problem
persists, contact your local ABB
representative.
64A1 Internal file load File read error. Reboot the control unit (using
parameter 96.08 Control board boot)
or by cycling power. If the problem
persists, contact your local ABB
representative
64A4 Rating ID fault Rating ID load error. Contact your local ABB
representative.
64A6 Adaptive program Error running the
adaptive program.
Check the auxiliary code (format
XXYY ZZZZ).
“XX” specifies the number of the state
(00=base program) and “YY” specifies
the number of the function block
(0000=generic error).
“ZZZZ” indicates the problem.
000A Program corrupted or
block non-existent
Restore the template program or
download the program to the drive.
000C Required block input
missing
Check the inputs of the block.
000E Program corrupted or
block non-existent
Restore the template program or
download the program to the drive.
0011 Program too large. Remove blocks until the error stops.
0012 Program is empty. Correct the program and download it
to the drive.
Code
(hex)
Fault / Aux. code Cause What to do