80 ACH580 Installation, Operation and Maintenance Manual
ACH580-01 Installation
0012 Motor too large for
advanced standstill ID
run.
Check that the motor and drive sizes
are compatible.
Contact your local ABB
representative.
0013 (Asynchronous motors
only)
Motor data error.
Check that the motor nominal value
settings in the drive are the same as
in the motor nameplate.
Contact your local ABB
representative.
FF63 STO diagnostics failure. SW internal
malfunction.
Reboot the control unit (using
parameter 96.08 Control board boot)
or by cycling power.
FF81 FB A force trip A fault trip command
has been received
through fieldbus
adapter A.
Check the fault information provided
by the PLC.
FF8E EFB force trip A fault trip command
has been received
through the embedded
fieldbus interface.
Check the fault information provided
by the PLC.
Code
(hex)
Fault / Aux. code Cause What to do