Parameters 105
Parameter listing
No. Name/Value Description Def/
FbEq16
01
01 Actual values
Basic signals for monitoring the drive.
All parameters in this group are read-only unless otherwise
noted.
01.01 Motor speed used Measured or estimated motor speed depending on which
type of feedback is used (see parameter 90.41 Motor
feedback selection). A filter time constant for this signa46l
can be defined by parameter 46.11 Filter time motor
speed.
-
-30000.00
…30000.00 rpm
Measured or estimated motor speed. See par.
46.01
01.02 Motor speed
estimated
Estimated motor speed in rpm. A filter time constant for
this signal can be defined by parameter 46.11 Filter time
motor speed.
-
-30000.00
…30000.00 rpm
Estimated motor speed. See par.
46.01
01.03 Motor speed % Shows the value of 01.01 Motor speed used in percent of
the synchronous speed of the motor.
10 = 1%
-1000.00 …
1000.00%
Measured or estimated motor speed. See par.
46.01
01.04 Encoder 1 speed
filtered
Speed of encoder 1 in rpm. A filter time constant for this
signal can be defined by parameter 46.11 Filter time motor
speed.
-
-30000.00
…30000.00 rpm
Encoder 1 speed. See par.
46.01
01.05 Encoder 2 speed
filtered
Speed of encoder 2 in rpm. A filter time constant for this
signal can be defined by parameter 46.11 Filter time motor
speed.
-
-30000.00
…30000.00 rpm
Encoder 2 speed. See par.
46.01
01.06 Output frequency Estimated drive output frequency in Hz. A filter time
constant for this signal can be defined by parameter 46.12
Filter time output frequency.
-
-500.00
…500.00 Hz
Estimated output frequency. See par.
46.02
01.07 Motor current Measured (absolute) motor current in A. -
0.00…30000.00 A Motor current. See par.
46.05
01.10 Motor torque Motor torque in percent of the nominal motor torque. See
also parameter 01.30 Nominal torque scale.
A filter time constant for this signal can be defined by
parameter 46.13 Filter time motor torque.
-
-1600.0…1600.0% Motor torque. See par.
46.03
01.11 DC voltage Measured DC link voltage. -
0.00…2000.00 V DC link voltage. 10 = 1 V
01.13 Output voltage Calculated motor voltage in V AC. -
0...2000 V Motor voltage. 1 = 1 V