Parameters 295
54.30 FBA B mapping file
ver
Displays the fieldbus adapter module mapping file revision
stored in the memory of the drive in decimal format.
This parameter is read-only.
-
0…65535 Mapping file revision. 1 = 1
54.31 D2FBA B comm
status
Displays the status of the fieldbus adapter module
communication.
-
Not configured Adapter is not configured. 0
Initializing Adapter is initializing. 1
Time out A timeout has occurred in the communication between the
adapter and the drive.
2
Configuration error Adapter configuration error: mapping file not found in the
file system of the drive, or mapping file upload has failed
more than three times.
3
Off-line Fieldbus communication is off-line. 4
On-line Fieldbus communication is on-line, or fieldbus adapter has
been configured not to detect a communication break. For
more information, see the documentation of the fieldbus
adapter.
5
Reset Adapter is performing a hardware reset. 6
54.32 FBA B comm SW ver Displays the patch and build versions of the adapter
module firmware in format xxyy, where xx = patch version
number, yy = build version number.
Example: C802 = 200.02 (patch version 200, build
version 2).
Patch and build versions of adapter module firmware. -
54.33 FBA B appl SW ver Displays the major and minor versions of the adapter
module firmware in format xyy, where x = major revision
number, yy = minor revision number.
Example: 300 = 3.00 (major version 3, minor version 00).
Major and minor versions of adapter module firmware. -
55
55 FBA B data in
Selection of data to be transferred from drive to fieldbus
controller through fieldbus adapter B.
55.01 FBA B data in1 Parameters 55.0155.12 select data to be transferred
from the drive to the fieldbus controller through fieldbus
adapter B.
None
None None. 0
CW 16bit Control Word (16 bits) 1
Ref1 16bit Reference REF1 (16 bits) 2
Ref2 16bit Reference REF2 (16 bits) 3
SW 16bit Status Word (16 bits) 4
Act1 16bit Actual value ACT1 (16 bits) 5
Act2 16bit Actual value ACT2 (16 bits) 6
CW 32bit Control Word (32 bits) 11
Ref1 32bit Reference REF1 (32 bits) 12
Ref2 32bit Reference REF2 (32 bits) 13
SW 32bit Status Word (32 bits) 14