EasyManua.ls Logo

ABB ACS880 PCP - Fault Functions

ABB ACS880 PCP
494 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters 241
Enable Overvoltage control enabled. 1
30.31 Undervoltage control Enables the undervoltage control of the intermediate DC
link. If the DC voltage drops due to input power cut off, the
undervoltage controller will automatically decrease the
motor torque in order to keep the voltage above the lower
limit. By decreasing the motor torque, the inertia of the
load will cause regeneration back to the drive, keeping the
DC link charged and preventing an undervoltage trip until
the motor coasts to a stop. This will act as a power-loss
ride-through functionality in systems with high inertia, such
as a centrifuge or a fan.
Enable
Disable Undervoltage control disabled. 0
Enable Undervoltage control enabled. 1
31
31 Fault functions
Configuration of external events; selection of behavior of
the drive upon fault situations.
31.01 External event 1
source
Defines the source of external event 1.
See also parameter 31.02 External event 1 type.
0 = Trigger event
1 = Normal operation
Inactive (true);
DI6 (95.20 b8)
Active (false) 0. 0
Inactive (true) 1. 1
DIIL DIIL input (10.02 DI delayed status, bit 15). 2
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 3
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 4
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 5
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 6
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 7
DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 8
DIO1 Digital input/output DIO1 (11 .02 DIO delayed status, bit 0). 11
DIO2 Digital input/output DIO2 (11 .02 DIO delayed status, bit 1). 12
Other [bit] Source selection (see Terms and abbreviations on
page 101).
-
31.02 External event 1 type Selects the type of external event 1. Fault
(95.20 b8)
Fault The external event generates a fault. 0
Warning The external event generates a warning. 1
Warning/Fault If the drive is modulating, the external event generates a
fault. Otherwise, the event generates a warning.
3
31.03 External event 2
source
Defines the source of external event 2. See also
parameter 31.04 External event 2 type.
For the selections, see parameter 31.01 External event 1
source.
Inactive (true),
DIIL
(95.20 b8)
31.04 External event 2 type Selects the type of external event 2.
Fault The external event generates a fault. 0
Warning The external event generates a warning. 1
No. Name/Value Description Def/