242 Parameters
Warning/Fault If the drive is modulating, the external event generates a
fault. Otherwise, the event generates a warning.
3
31.05 External event 3
source
Defines the source of external event 3. See also
parameter 31.06 External event 3 type.
For the selections, see parameter 31.01 External event 1
source.
Inactive (true)
31.06 External event 3 type Selects the type of external event 3.
Fault The external event generates a fault. 0
Warning The external event generates a warning. 1
Warning/Fault If the drive is modulating, the external event generates a
fault. Otherwise, the event generates a warning.
3
31.07 External event 4
source
Defines the source of external event 4. See also
parameter 31.08 External event 4 type.
For the selections, see parameter 31.01 External event 1
source.
Inactive (true)
31.08 External event 4 type Selects the type of external event 4.
Fault The external event generates a fault. 0
Warning The external event generates a warning. 1
Warning/Fault If the drive is modulating, the external event generates a
fault. Otherwise, the event generates a warning.
3
31.09 External event 5
source
Defines the source of external event 5. See also
parameter 31.10 External event 5 type.
For the selections, see parameter 31.01 External event 1
source.
Inactive (true)
31.10 External event 5 type Selects the type of external event 5.
Fault The external event generates a fault. 0
Warning The external event generates a warning. 1
Warning/Fault If the drive is modulating, the external event generates a
fault. Otherwise, the event generates a warning.
3
31.11 Fault reset selection Selects the source of an external fault reset signal. The
signal resets the drive after a fault trip if the cause of the
fault no longer exists.
0 -
>
1 = Reset
Note: A fault reset from the fieldbus interface is always
observed regardless of this parameter.
Not selected
Not selected 0. 0
Selected 1. 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 4
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 6
DI6 Digital input DI6 (10.02
DI delayed status, bit 5). 7
DIO1 Digital input/output DIO1 (11.02 DIO delayed status, bit 0). 10
DIO2 Digital input/output DIO2 (11.02 DIO delayed status, bit 1). 11
FBA A MCW bit 7 Control word bit 7 received through fieldbus interface A. 30
No. Name/Value Description Def/
FbEq16