144 Parameters
12.26 AI2 filter time Defines the filter time constant for analog input AI2. See
parameter 12.16 AI1 filter time.
0.100 s
0.000…30.000 s Filter time constant. 1000 = 1 s
12.27 AI2 min Defines the minimum site value for analog input AI2.
Set the value actually sent to the drive when the analog
signal from plant is wound to its minimum setting.
See also parameter 12.01 AI tune.
0.000 mA or V
-22.000
…22.000 mA or V
Minimum value of AI2. 1000 = 1 mA
or V
12.28 AI2 max Defines the maximum site value for analog input AI2.
Set the value actually sent to the drive when the analog
signal from plant is wound to its maximum setting.
See also parameter 12.01 AI tune.
20.000 mA or
10.000 V
-22.000
…22.000 mA or V
Maximum value of AI2. 1000 = 1 mA
or V
12.29 AI2 scaled at AI2 min Defines the real value that corresponds to the minimum
analog input AI2 value defined by parameter 12.27 AI2
min. (Changing the polarity settings of 12.29 and 12.30
can effectively invert the analog input.)
0.000
-32768.000
…32767.000
Real value corresponding to minimum AI2 value. 1 = 1
12.30 AI2 scaled at AI2 max Defines the real value that corresponds to the maximum
analog input AI2 value defined by parameter 12.28 AI2
max. See the drawing at parameter 12.29 AI2 scaled at
AI2 min.
100.000
-32768.000
…32767.000
Real value corresponding to maximum AI2 value. 1 = 1
13
13 Standard AO
Configuration of standard analog outputs.
13.11 AO1 actual value Displays the value of AO1 in mA.
This parameter is read-only.
-
0.000…22.000 mA Value of AO1. 1000 = 1 mA
No. Name/Value Description Def/
FbEq16
12.30
12.28
12.27
12.29
AI
in
(12.21)
AI
scaled
(12.22)