PCP/ESP control start-up 23
PCP/ESP control start-up
Contents of this chapter
This chapter contains the start-up sequence of the PCP/ESP control program.
PCP/ESP control start-up
This section contains the following alternative control schemes for starting up the
drive with the control program:
• High pressure switch set up
• Optional speed reduction at maximum torque
In addition, this section describes how to configure the following program features:
The checklist for PCP/ESP control start up is given below:
I/O wiring
Connect the digital and analog I/Os according to the wiring diagram shown
in page 96.
I/O wiring parameter settings
Select the source of the start for external
control location 1 (EXT1).
20.01 Ext1 commands
Select the level-triggered signal type. 20.02 Ext1 start trigger
type
Select the start signal. By default, the drive
starts/stops according to the status of digital
input DI1 (0 = Stop, 1 = Start).
20.03 Ext1 in1 source