24 PCP/ESP control start-up
Select the way motor is stopped when the run
enable signal switches off.
20.11 Run enable stop
mode
Select the source of the external run enable
signal. If the run enable signal is switched off,
the drive will not start.
20.12 Run enable 1
source
Select the way motor is stopped when an
emergency stop command is received.
21.04 Emergency stop
mode
Select the source of the emergency stop
signal.
21.05 Emergency stop
source
Select the source of an external fault reset
signal. The signal resets the drive after a fault
trip if the cause of the fault no longer exists.
31.11 Fault reset selection
Basic pump set up
The following information is required to complete the set up:
Maximum rod torque in lbft or Nm.
Enable the pump functions. 74.01 Pump enable
Define the transmission reduction ratio.
Note: Not applicable for ESP.
74.03 Gear reduction ratio
Select the reference type between motor
speed or pump speed.
Note: Not applicable for ESP.
74.04 Speed ref type
Select the source for the speed reference.
Note: If parameter 74.05 Speed ref source is
selected as AI1 scaled, set the minimum and
maximum values of AI1.
74.05 Speed ref source
12.19 AI1 scaled at AI1
min
12.20 AI1 scaled at AI1
max
Set the speed reference if parameter 74.05
Speed ref source is selected as Constant ref
(Prpm, rpm or Hz).
74.06 Speed ref
Gear reduction ratio
pump sheave diameter
*
gear box ratio
motor sheave diameter
=