PCP/ESP program features 49
Warnings: D208 Backspin limit and D209 Backspin active
Faults: -
Start delay
Start delay function blocks any start command when stop command is given. User
can enable this function using parameter 80.11 Start delay enable. Pump will not able
to make start during defined time period 80.12 Start delay time. This delay time has to
be equal or longer then time period needed to complete shutdown process.
Time remained to allow drive to start is indicating in actual signal 09.12 Start delay
remain.
If drive is stopped due to power failure and then after power supply is retained, the
stopped time period will be deducted from start delay time. In case, if battery of ZCU
board is empty, time will not be deducted from start delay time in case of power
failure.
Settings
Parameters: 80.11 Start delay enable and 80.12 Start delay time.
Signals: 09.12 Start delay remain, 09.13 Backspin status word (bits 10 and 11).
Warnings: D20C Start delay active.
Faults: -

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS880 PCP and is the answer not in the manual?

ABB ACS880 PCP Specifications

General IconGeneral
Output currentUp to 5200 A
Input voltage380-690 V
Power range5600 kW
Cooling methodAir or liquid
Protection classIP21, IP54
Communication interfacesEthernet, CANopen

Related product manuals