Parameters 291
50.47 FBA B actual value 1 Displays raw (unmodified) actual value ACT1 sent by
fieldbus adapter B to the master (PLC) if debugging is
enabled by parameter 50.42 FBA B debug mode.
This parameter is read-only.
-
-2147483648
…2147483647
Raw ACT1 sent by fieldbus adapter B to master. -
50.48 FBA B actual value 2 Displays raw (unmodified) actual value ACT2 sent by
fieldbus adapter B to the master (PLC) if debugging is
enabled by parameter 50.42 FBA B debug mode.
This parameter is read-only.
-
-2147483648
…2147483647
Raw ACT2 sent by fieldbus adapter B to master. -
50.51 FBA B timelevel sel Selects the communication time levels.
In general, lower time levels of read/write services reduce
CPU load. The table below shows the time levels of the
read/write services for cyclic high and cyclic low data with
each parameter setting.
* Cyclic high data consists of fieldbus Status word, Act1
and Act2.
** Cyclic low data consists of the parameter data mapped
to parameter groups 55 FBA B data in and 56 FBA B data
out, and acyclic data.
Control word, Ref1 and Ref2 are handled as interrupts
generated on receipt of cyclic high messages.
Normal
Normal Normal speed. 0
Fast Fast speed. 1
Very fast Very fast speed. 2
Monitoring Low speed. Optimized for PC tool communication and
monitoring usage.
3
51
51 FBA A settings
Fieldbus adapter A configuration.
51.01 FBA A type Displays the type of the connected fieldbus adapter
module.
0 = Module is not found or is not properly connected, or is
disabled by parameter 50.01 FBA A enable; 1 = FPBA;
32 = FCAN; 37 = FDNA; 101 = FCNA, 128 = FENA-11/21;
135 = FECA; 136 = FEPL; 485 = FSCA.
This parameter is read-only.
-
No. Name/Value Description Def/
FbEq16
Selection Cyclic high * Cyclic low **
Monitoring 10 ms 2 ms
Normal 2 ms 10 ms
Fast 500 µs 2 ms
Very fast 250 µs 2 ms