448 Fieldbus control through the embedded fieldbus interface (EFB)
8 JOGGING_1 1 Accelerate to jogging 1 reference.
Notes:
Bits 4…6 must be 0.
See also section Jogging (page 69).
0 Jogging 1 disabled.
9 JOGGING_2 1 Accelerate to jogging 2 reference.
See notes at bit 8.
0 Jogging 2 disabled.
10 REMOTE_
CMD
1 Fieldbus control enabled.
0 Control Word <> 0 or Reference <> 0: Retain last Control
Word and Reference.
Control Word = 0 and Reference = 0: Fieldbus control
enabled. Reference and deceleration/acceleration ramp
are locked.
11 EXT_CTRL_
LOC
1 Select External Control Location EXT2. Effective if the
control location is parameterized to be selected from the
fieldbus.
0 Select External Control Location EXT1. Effective if the
control location is parameterized to be selected from the
fieldbus.
12…15 Reserved